Interlink Electrical Connections 

Up to 12 units may be interlinked together in the following manner: 

 
Optional mains power application 

The MCP/Sounder can also be powered from a Mains 24VDC PSU (minimum of 150mA). A schematic is shown 
below: 

 

2. Reset and Test 

The Call Point is a Type-A (Direct type see EN54 Pt.11) contains a resettable 
element, which latches in position when operated and does not need to be replaced. 
The unit may be reset by inserting the key as shown and turning it clockwise until 
the element clicks back into place. Testing the Call Point may be carried out either 
by pressing the element or by using the key in the same manner as for resetting but 
without having pressed the element 

 

 

3. Technical Data 

Class of MCP:   

Type-A (Direct type see EN54 Pt.11) 

Dimensions: 

 

 W87mm x H87mm ,  Flush depth protruding= 25mm,  Surface depth= 53mm 

Operating temperature:   -5ºC to 65ºC 
Voltage Range:   12 to 30V DC 
Operating Current: 

 Quiescent, No Current 

 

 

 

 Alarm 10mA @ 24V, Dual Tone UK Evacuate   – 800 & 970 Hz 

 

Sound Pressure Outputs: 85dB(A)  @24V 

 

 

Battery Type:   

  12V - GP23A, VR22, MN21 

 
 
 
 