FIRE DAMPERS

364

365

Design changes reserved

*Flexible conectors are shipped unassembled. 

Cover grille

If fire damper is to be ducted only from one side, other end must have a cover grille. Cover grills have cross sectional free area ap-

proximately 70%. When cover grilles are being installed very important is to install extension peace if necessary (see table 2). 

**Extension peace is not supplied 

*Cover grilles are shipped unassembled. 

**Extension peace is not supplied 

Flexible connectors

 

 Ventilation ducts must be installed in such manner that don’t oppose loads on fire damper or wall in case of fire. This is important 

when dumper is installed and sealed with mineral wool. Using flexible connectors when connecting fire dampers to ducts can elimi-

nate that problem. Flexible connectors are available on demand in dimensions same as fire dampers. 

When flexible connectors are being installed very important is to install extension peace if necessary (see table 2).  

ACCESSORIES

Suspension for mortarless installation

Suspension systems are required for the dry mortarless installation of the fire damper with mineral wool in solid walls, flexible walls 

and ceiling slabs. Fire dampers can be suspended from solid ceiling slabs using adequately sized threaded rods. Load the suspen-

sion system only with the weight of the fire damper. Ducts must be suspended separately. Suspension systems longer than 1.5 m 

require fire-resistant insulation. 

Threaded rod (M10) , galvanized steel
Washer, galvanized steel
Nut, , galvanized steel
Bracket, 45x30x1,5 mm, , galvanized steel
L shaped profile (50x50x1) secured with self tapping screw to damper housing

1
2
3
4

1

3

2

4

5

425

x

y

425

x

x

5

Øn, mm (fire 
damper diameter)

X/Y, mm (exten-
sion piece length)

400

-/65

450

-/90

500

-/115

560

30/145

630

65/180

Table 2

For ceiling instal-
lation, brackets on 
the bottom are used 
to support wool 
from falling down.

Wall installation

Ceiling installation

Summary of Contents for FD25-E

Page 1: ...355 www klimaoprema hr FDC25 FIRE DAMPER 7 S4 v 2 9 en...

Page 2: ...ased 361 Installation in a flexible wall mortar based 361 Installation in ceiling mortar based 362 Installation in a rigid wall mortarless 362 Installation in a flexible wall mortarless 363 Installati...

Page 3: ...with greater fire resistance can also be used Fire damper should be installed according instal lation manual which can be found within this document Table 1 Dimensions FIRE DAMPER FDC25 Standard diam...

Page 4: ...sm type R manual mechanism E230 solenoid actuator AC230V E24 solenoid actuator AC 24V M230 electric actuator AC230V M24 electric actuator AC DC 24V Options s electric limit switches indicating damper...

Page 5: ...er blade 2 electric actuator Belimo BLF 3 thermo electric tripping device 72 C 4 intumescent strip 5 Options M230 electric actuator AC 230V M24 electric actuator AC DC 24V FDC25 R cylindrical fire dam...

Page 6: ...zed steel but on demand can be made from Galvanized steel and powder coated Stainless steel Stainless steel and powder coated Fire damper for areas with potentially explosive atmospheres are also avai...

Page 7: ...FDC25 Wall according to table 1 Installation steps Recommended wall opening for fire damper installation is 160mm but openings from 80 200 mm can also be used Insert fire damper into wall and secure o...

Page 8: ...mper blade mobility preform an opening and closing test 3 4 Fire damper FDC25 Wall according to table 1 Installation in a rigid wall mortarless 1 2 3 4 Installation steps Recommended ceiling opening f...

Page 9: ...ing test 3 4 Fire damper FDC25 Wall according to table 1 Installation material Fire damper FDC25 Mineral wool 140kg m3 Fire protection coating HILTI weichschott system Installation steps Recommended c...

Page 10: ...ble connectors are being installed very important is to install extension peace if necessary see table 2 ACCESSORIES Suspension for mortarless installation Suspension systems are required for the dry...

Page 11: ...e supplied with one or two limit switches switches can also be fitted later DAMPER OPEN DAMPER CLOSED Fire damper is shipped with closed damper blade Fire damper with manual actuating mechanism is ope...

Page 12: ...not move the damper into closed position after power failure ther moelectric fuse switch for checking for proper functioning handle for manual opening Belimo BLF24 T i BF24 T supply via safety isolati...

Page 13: ...per Level Digital field controller K FC24 Digital field controller to control and monitor up to 4 motorized fire dampers and 4 smoke detectors Communication Modbus RTU RS 485 The safety function of th...

Reviews: