FIRE DAMPERS

366

367

Design changes reserved

BELIMO

BLF230

Damper is delivered in closed position. When electric actuator is connected to the power supply damper will open. When the damper

reaches the end position (damper open), in which is it blocked, the electromotor will stop. Closing fire damper takes place automati-

cally when a power failure occurs. Thermal tripping device that comes with fire damper causes power circuit break at a temperature

of 72 °C (inside or outside duct). If checking is needed for proper fuctioning of fire damper, pushing the switch on the thermal tripping

device will close damper. When switch on tripping device is released, the damper will open.

Damper can be opened without connecting to a voltage with enclosed handle turning in the direction of the arrow on electric acuator

(clockwise). Damper can be locked in the desired position by fast turning back handle a quarter of a turn (counterclockwise).

To unlock the electromotor, turn handle clockwise for a quarter of a turn. If the handle is released, damper will be closed by return

spring. When damper is opened manually, electric actuator will not move the damper into closed position after power failure (ther-

moelectric fuse).

switch for checking for
proper functioning

handle for manual opening

Belimo BLF24-T i BF24-T supply via

safety isolation transformer

1

negative (direct-current) or neutral (alternating current)

2

positive (direct-current) or faze (alternating current)

S1

common micro switch closed damper

S2

normally closed micro switch closed damper

S3

normally open micro switch closed damper

S4

common micro switch open damper

S5

normally closed micro switch open damper

S6

normally open micro switch open damper

Tf1

temperature sensor on the outer side of the duct (ambi-
enttemperature) max. 72°C

Tf2

temperature sensor on the inner side of the duct (tem-
perature in the duct) max. 72°C

Tf3

temperature sensor on the inner side of the duct (tem-
perature in the duct) max. 72°C

Type of Belimo actuator

BLF24-T

BLF230-T

Nominal 
voltage /
power con-
sumption

voltage

AC/DC 24V, 50/60Hz

AC 230V, 50/60Hz

opening

5 W

8 W

holding

2,5 W

3 W

for wire sizing

7 VA

12,5 VA

End switch

1 mA...3 A (0,5 A), 

DC 5 V...AC 250V

1 mA...3 A (0.5 A), 

DC 5 V...AC 250 V

Running 
time

motor

40...75 s

40...75 s

spring-return

~20 s

~20 s

Ambient temperature range

max. 50°C

S1 S2 S3 S4 S5 S6

 <5°

 <80°

2

1

T

~

BAE72B-S

Tf1

Tf2

Tf3 LED

Electrical characteristics and wiring scheme for Belimo electrical actuator

Summary of Contents for FD25-E

Page 1: ...355 www klimaoprema hr FDC25 FIRE DAMPER 7 S4 v 2 9 en...

Page 2: ...ased 361 Installation in a flexible wall mortar based 361 Installation in ceiling mortar based 362 Installation in a rigid wall mortarless 362 Installation in a flexible wall mortarless 363 Installati...

Page 3: ...with greater fire resistance can also be used Fire damper should be installed according instal lation manual which can be found within this document Table 1 Dimensions FIRE DAMPER FDC25 Standard diam...

Page 4: ...sm type R manual mechanism E230 solenoid actuator AC230V E24 solenoid actuator AC 24V M230 electric actuator AC230V M24 electric actuator AC DC 24V Options s electric limit switches indicating damper...

Page 5: ...er blade 2 electric actuator Belimo BLF 3 thermo electric tripping device 72 C 4 intumescent strip 5 Options M230 electric actuator AC 230V M24 electric actuator AC DC 24V FDC25 R cylindrical fire dam...

Page 6: ...zed steel but on demand can be made from Galvanized steel and powder coated Stainless steel Stainless steel and powder coated Fire damper for areas with potentially explosive atmospheres are also avai...

Page 7: ...FDC25 Wall according to table 1 Installation steps Recommended wall opening for fire damper installation is 160mm but openings from 80 200 mm can also be used Insert fire damper into wall and secure o...

Page 8: ...mper blade mobility preform an opening and closing test 3 4 Fire damper FDC25 Wall according to table 1 Installation in a rigid wall mortarless 1 2 3 4 Installation steps Recommended ceiling opening f...

Page 9: ...ing test 3 4 Fire damper FDC25 Wall according to table 1 Installation material Fire damper FDC25 Mineral wool 140kg m3 Fire protection coating HILTI weichschott system Installation steps Recommended c...

Page 10: ...ble connectors are being installed very important is to install extension peace if necessary see table 2 ACCESSORIES Suspension for mortarless installation Suspension systems are required for the dry...

Page 11: ...e supplied with one or two limit switches switches can also be fitted later DAMPER OPEN DAMPER CLOSED Fire damper is shipped with closed damper blade Fire damper with manual actuating mechanism is ope...

Page 12: ...not move the damper into closed position after power failure ther moelectric fuse switch for checking for proper functioning handle for manual opening Belimo BLF24 T i BF24 T supply via safety isolati...

Page 13: ...per Level Digital field controller K FC24 Digital field controller to control and monitor up to 4 motorized fire dampers and 4 smoke detectors Communication Modbus RTU RS 485 The safety function of th...

Reviews: