background image

FIRE DAMPERS

360

361

Design changes reserved

80

• 

Recommended wall opening for fire damper installation 

is Øn+ 160mm, but openings from Øn +80*…200 mm 

can also be used 

(*decrease under specified value in 

opening size is allowed if there is sufficient room for 

seal installation)

• 

Insert fire damper into wall and secure on wall face with 

two hinges that are placed on the top of fire damper 

casing. Hinges are used to hold only damper during 

installation! (for max. distance from wall 80 mm) 

• 

Damper blade must be closed during installation 

• 

Space between casing and wall must be filled with 

mortar, gypsum or concrete

• 

Test the fire damper after the installation 

• 

During installation, manual or motorized mechanism 

must be protected from mortar, gypsum or concrete. 

After installation check for damper 
blade mobility, preform an opening and 
closing test.

Standard mortar or gypsum

1
2
3

Fire damper FDC25

Wall, according to table 1

Installation steps:

• 

Recommended wall opening for fire damper installation 

is 

Ø

 + 160mm, but openings from 

Ø

 + 80…200 mm 

can also be used 

• 

Insert fire damper into wall and secure on wall face with 

two hinges that are placed on the top of fire damper cas-

ing. Hinges are used to hold only damper during installa-

tion! (for max. distance from wall 80 mm)

• 

Damper blade must be closed during installation

• 

Space between casing and wall must be filled with mor-

tar or gypsum

• 

Mortar or gypsum must be covered with fire resistant 

boards that are secured onto wall face with screws

• 

Test the fire damper after the installation

• 

During installation, manual or motorized mechanism 

must be protected from mortar and dust. 

Standard mortar or gypsum

Masterboard thickness 20mm

Screw for gypsum plasterboard

1
2
3

After installation check for damper
blade mobility, preform an opening and
closing test.

4
5

Fire damper FDC25

Wall, according to table 1

INSTALLATION OPTIONS

Installation in a rigid wall (mortar based)

Installation in a flexible wall (mortar based)

1

2

3

1

2

3

4

5

Summary of Contents for FD25-E

Page 1: ...355 www klimaoprema hr FDC25 FIRE DAMPER 7 S4 v 2 9 en...

Page 2: ...ased 361 Installation in a flexible wall mortar based 361 Installation in ceiling mortar based 362 Installation in a rigid wall mortarless 362 Installation in a flexible wall mortarless 363 Installati...

Page 3: ...with greater fire resistance can also be used Fire damper should be installed according instal lation manual which can be found within this document Table 1 Dimensions FIRE DAMPER FDC25 Standard diam...

Page 4: ...sm type R manual mechanism E230 solenoid actuator AC230V E24 solenoid actuator AC 24V M230 electric actuator AC230V M24 electric actuator AC DC 24V Options s electric limit switches indicating damper...

Page 5: ...er blade 2 electric actuator Belimo BLF 3 thermo electric tripping device 72 C 4 intumescent strip 5 Options M230 electric actuator AC 230V M24 electric actuator AC DC 24V FDC25 R cylindrical fire dam...

Page 6: ...zed steel but on demand can be made from Galvanized steel and powder coated Stainless steel Stainless steel and powder coated Fire damper for areas with potentially explosive atmospheres are also avai...

Page 7: ...FDC25 Wall according to table 1 Installation steps Recommended wall opening for fire damper installation is 160mm but openings from 80 200 mm can also be used Insert fire damper into wall and secure o...

Page 8: ...mper blade mobility preform an opening and closing test 3 4 Fire damper FDC25 Wall according to table 1 Installation in a rigid wall mortarless 1 2 3 4 Installation steps Recommended ceiling opening f...

Page 9: ...ing test 3 4 Fire damper FDC25 Wall according to table 1 Installation material Fire damper FDC25 Mineral wool 140kg m3 Fire protection coating HILTI weichschott system Installation steps Recommended c...

Page 10: ...ble connectors are being installed very important is to install extension peace if necessary see table 2 ACCESSORIES Suspension for mortarless installation Suspension systems are required for the dry...

Page 11: ...e supplied with one or two limit switches switches can also be fitted later DAMPER OPEN DAMPER CLOSED Fire damper is shipped with closed damper blade Fire damper with manual actuating mechanism is ope...

Page 12: ...not move the damper into closed position after power failure ther moelectric fuse switch for checking for proper functioning handle for manual opening Belimo BLF24 T i BF24 T supply via safety isolati...

Page 13: ...per Level Digital field controller K FC24 Digital field controller to control and monitor up to 4 motorized fire dampers and 4 smoke detectors Communication Modbus RTU RS 485 The safety function of th...

Reviews: