8
| Circular fire damper user manual 03/2020
9
|
Circular fi
re damper user manual 03/2020
5.2.3 Gypsum blocks wall 70mm
The wall is composed of gypsum blocks (minimum density of 995kg/m
³), and with minimum thickness
of 70mm.
5.2.4 Gypsum blocks wall 100mm
The wall is composed of gypsum blocks (minimum density of 995kg/m
³), and with minimum thickness
of 100mm.
Place the damper in an opening
according to table (on pg. 6)
Fix damper and GKF gypsum boards
(12,5mm thick) to wall with screws
(screw hole is 6mm in diameter)
Fill the space between the damper
and the wall with mortar
Cover the mortar with GKF gypsum
boards (12,5 mm thick)
* The Kit is universal for
all dimensions and must
be cut to fit the specific
dimensions of the damper
Diameter of the
damper (mm) Mounting kit
100
60061429
125
60061430
160
60061431
200
60061432
250
60061433
315
60061435
355
60061436
400
60061437
450
60061438
500
60061439
560
60061440
630
60061441
710
60061442
800
60061443
Fix the damper to the wall using
screws (screw hole is 6mm in
diameter)
Fill the space between the damper
and the wall with mortar
Cover the mortar with GKF gypsum
boards (12,5 mm thick)
Place the damper in an opening
according to table (on pg. 6)
* The Kit is universal for
all dimensions and must
be cut to fit the specific
dimensions of the damper
Diameter of the
damper (mm) Mounting kit
100
60061429
125
60061430
160
60061431
200
60061432
250
60061433
315
60061435
355
60061436
400
60061437
450
60061438
500
60061439
560
60061440
630
60061441
710
60061442
800
60061443