background image

 

 3 

 

 

 

 

04.06.2019                                

explosion-proof roof fan

  WPA-D-N/Ex  

 

2.

 

Application 

WPA-D-N/Ex 

explosion

-

proof roof fans

 

are intended for use  in areas of explosion 

risk, where 

explosive atmosphere, (i.e. mixture of flammable substances in form of gas and vapour with  
the air, whereby after ignition 

– in atmospheric conditions

  

– the burning mass would expand  

within the whole non-burning mixture)

  

is likely to occur. The fans have been constructed for 

application within temperature range -20 up to 40

C.  The forwarded air must be dry,  of dus- 

tiness not exceeding 0,3 g/m

3

,  without viscous,  aggressive contaminants  and of maximum 

tempe60

C. 

Increased fan pressure guarantees their application  in systems with local exhausts and filte- 
ring units, and additionally in ventilation ductings of significant flow resistances. 

According to

 

the 2014/34/EC ATEX Directive  and

 

EN ISO 80079-36  the

 device carries the  

level 

of 

protection

HIGH

” –  

as a device classified

 

for 

Group

 II, 

Category

 2,

  

and it can  

work in areas where explosive atmospheres are likely to occur. 

The fan

 can be applied  

in zones 1

2

 (

G

).

  

The appliance is marked on the nominal data plate: 

 

II 2 G c Ex e II T3

 

Marking

  

of

  

the

  

operational

  

conditions

  

of

  

the device

:

  group / category / hazard / class

.

 

 

  marking for explosion proof properties of the appliance, 

  group II

  

– the device

  

is

  

designed

  

for

  

on-ground work,

 

 

in factories,

  

in areas

  

of

  

explosion 

hazard,  

but this cannot be methane 

(

firedamp

)

 

hazard

 

neither carbon dust occurrence, 

  category 2

 

– the device is designed

  

for application in areas  where 

explosive atmosphe- 

res are likely to occur

  gas hazard G

 

c

” – a sort of protection against ignition – constructional protection, 

  Ex

 

– mark of the electrical device – 

constructed

 

and

 tested according 

to the European Stan-

 

dards for work in areas of explosion hazard, 

  execution

 

e

” – type of construction of the motor (a motor of increased safety) 

 

gas explosion 

group

 II

 

– 

occurring

 in on-ground factories 

– the fans are constructed accor- 

ding to 

the PN-EN 14986:2009

, whereby they can be applied for gases in explosion groups 

IIA

 and 

IIB

 and 

hydrogen

 

temperature

 class T3

 

 the surface

 temperature 

of any

 part 

of the

 appliance should 

not

 

ex-

ceed 

200ºC

 (during the normal operation).  The device can be used safely

  

in explosive at-

mospheres

  

belonging to temperature classes 

T1

T2

T3

 

3.

 

Reservations of Producer 

A

.

 

Manufacturer accepts no liability

  

for any consequences following from the operational use 

that is in contradiction to the purpose of application. 

B

.

 

Installing of

 any additional elements not belonging to the normal device structure (

or acces

sory set) is not acceptable. 

C

.

 

Do not undertake

  

any structural changes  or constructional modifications on the device on 

one

’s own. 

D

.

 

Protect the appliance’s housing from mechanical damage. 

E

.

 

Prior to

 

installing

 check the load carrying capacity 

of the building structure

  

where the device  

will be mounted.  Unsure mounting could cause hazard to personnel/people in vicinity and  
effect in damage of the device. 

 

F

Do not use

 the fan

 

for 

conveying

 the air

 containing viscous impurities that 

could deposit 

(

build up

)

  

on the device surface,  especially on the impeller. 

G

Neither use it  for forwarding the air  with aggressive pollutants which will 
destructively effect the device structure. 

 

 

Summary of Contents for 808W09

Page 1: ...on 7 6 Assembly and Start up 7 7 Operational Use 10 8 Troubleshooting Guide 11 9 Maintenance 11 10 Occupational Health and Safety 11 11 Transport and Storage 12 12 Terms of warranty 12 13 Sample of the Declaration of Conformity 13 808W09 WPA 5 D N Ex 04 06 2019 EN 808W10 WPA 6 D N Ex 04 06 2019 EN 808W11 WPA 7 D N Ex 04 06 2019 EN 808W12 WPA 8 D N Ex 04 06 2019 EN 808W13 WPA 9 D N Ex 04 06 2019 EN...

Page 2: ...ncil of February 26th 2014 on the harmonisation of the laws of Member States relating to equipment and protective systems intended for use in potentially explosive atmospheres Journal of Laws EC L96 of 29 03 2014 Additionally the appliance meets following harmonized standard EN ISO 12100 2012 Safety of machinery Basic concepts general principles for design Risk assessment and risk reduction EN 602...

Page 3: ...re explosive atmosphe res are likely to occur gas hazard G c a sort of protection against ignition constructional protection Ex mark of the electrical device constructed and tested according to the European Stan dards for work in areas of explosion hazard execution e type of construction of the motor a motor of increased safety gas explosion group II occurring in on ground factories the fans are c...

Page 4: ...th the applied silencer TK L 500 mm installed at the fan inlet weigh of the fan a b a with horizontal outlet b with vertical outlet 1 max temperature of the forwarded air is 60ºC maximum temperature in the work zone 40ºC 2 max dustiness of the forwarded air should not exceed 0 3 g m3 Fig No 1 WPA D N Ex Flow charts Type Synchro nous rotations Supply voltage Motor rate Ingress protect tion Acoustic...

Page 5: ...E mm F mm n pcs G mm H mm J mm WPA 5 D N Ex 905 525 60 160 160 194 6 6 5 500 140 WPA 6 D N Ex 915 550 60 160 160 194 6 6 5 500 140 WPA 7 D N Ex 965 570 60 200 160 194 6 6 5 535 155 WPA 8 D N Ex 990 600 60 200 200 224 234 246 8 6 8 9 0 6 5 9 0 535 155 WPA 9 D N Ex 1030 665 60 200 200 224 234 246 8 6 8 9 0 6 5 9 0 605 155 WPA 10 D N Ex 1050 675 100 250 250 275 8 9 0 720 232 ...

Page 6: ... N Ex 815 570 60 200 160 194 6 6 5 840 155 WPA 8 D N Ex 840 600 60 200 200 224 234 246 8 6 8 9 0 6 5 9 0 840 155 WPA 9 D N Ex 880 665 60 200 200 224 234 246 8 6 8 9 0 6 5 9 0 840 155 WPA 10 D N Ex 960 675 100 250 250 275 8 9 0 960 232 Table No 4 Specification of types of elbows for fans with vertical outlet Type of the fan Elbow Type of the elbow Weight kg WPA 5 D N KL 160 WPA 1 8 WPA 6 D N KL 160...

Page 7: ...ing pieces ought to be fastened to the ventilation system by means of flexible connectors of antistatic material The way of fastening of the connections depends on the established technologies of the system execution and should be specified at the site of installing User performing the assembly is strictly responsible for full compli ance with the provisions of EN ISO 13857 6 1 Guidelines of insta...

Page 8: ...temperature 20ºC up to 40ºC 5 Insulation class F 6 To the fan housing connect the grounding cable of length 400mm ended with a KOI terminal 7 Installations and devices for use in areas of explosion risk should be executed according to arrangements of the 2014 34 EC ATEX Directive valid regulations and standards S1 isolating switch in Ex execution It is suggested to install it near the fan The appl...

Page 9: ... a check if all the mechanical connections are carried out correctly b check the correctness of electrical connections and phase sequence c examine the correctness of the connection between the motor and PE protective cable After the device is started up check if the impeller rotation sense is according to the arrow on the housing ...

Page 10: ...t temperature exceeds 40 C Consequences of incorrect use a damage of bearings b damages caused by corrosion c loss in balance of the rotating elements d vibrations e deformations f damages caused by friction Risks which can occur due to improper use damages or other defects caused by burst of the impeller break of the shaft fatigue crack of the material ignition and explosion caused by sparks In c...

Page 11: ...f technical revision carry out following steps as a routine keep clean the inlet grill periodically examine and tighten up the mechanical and electrical connections moreover when defective function is by noise or visually spotted undertake the revision of the as sembly execute the revision of the fan motor according to the instructions of its manufacturer Within the scope of maintenance clean the ...

Page 12: ...ed in foil and placed on pallet During loading re loading and transport the device neither should be thrown nor knocked down Do not put any load on top of the device It is inadmissible to put one device on top of another stacking During the transport protect them from atmospheric factors weather conditions and from mechanical damage The fan must be stored in dry rooms and areas of efficient ventil...

Page 13: ...ery Electrical equipment of machines Part 1 Gene ral requirements EN ISO 13857 2010 Safety of machinery Safe distances to prevent hazard zones from be ing reached by upper and lower limbs EN 80079 0 2013 A11 2014 Electrical appliances in areas of gas explosion risk Part 0 General re quirements EN 60079 7 2016 02 Electrical appliances for areas of gas explosion hazard Part 7 Increased safety constr...

Page 14: ...14 explosion proof roof fan WPA D N Ex 04 06 2019 NOTES ...

Page 15: ...15 04 06 2019 explosion proof roof fan WPA D N Ex NOTES ...

Page 16: ...16 explosion proof roof fan WPA D N Ex 04 06 2019 NOTES ...

Reviews: