background image

 

 

 

 

 

 

25.01.2019 

    

Roof Fans

  SMART-EC-1300 

 

 

8.

 

Troubleshooting Guide 

Table No.2 

 

Problem 

Possible reason 

Corrective action  

1. 

Sudden vibrations of the fan  Obstacle objects reducing the  Disconnect the fan from the 

 

are occurring. 

air flow got stack within the  

power supply system, take 

 

 

impeller. 

off the hood and remove the 

 

 

 

obstacle. 

 

 

The impeller is faulty. 

Replace the impeller for new. 

 

 

 

9.

 

Maintenance 

The construction and a solid execution of the fans guarantee their operational use, without con- 
stant routine maintenance,  provided that their operational use is correct. 

 

To 

obtain 

correct functional performances and to meet 

the safety rules, it is recommended to sub-

 

mit the fan to technical revision in regular periods of time  (i.e. once a year).  
During the revision take into account the function of the fan as well as its technical state. 

 

 

 

 All the activities connected with

 technical revisions on the fan have to be 

carried out 

exclusively by an authorised person with adequate

 qualifications

  and

 necessa-

rily after disconnection from the power supply system

 
Additionally, observe the rules 

of Occupational 

Health and Safety. 

(

Non-compliance

 of the 

rules could result in threat to life and health of the employees

).

 

 

To disconnect the fan from the

 master circuit

 of the power 

supply,

  

use the

 isolating 

switch 

(

IS

)

, which should be ordered 

and

 

installed by User

. Isolating switch ought to be installed 

within reach of the servicer

 

Isolating 

switches (IS) are offered by KLIMAWENT S.A.

 as additional accessory. The way of con-

nection is shown in the operation manual of the insolating switch (IS). 

 

There are subsequent activities within the range of technical revision: 

●  examine and tighten up the mechanical- and electrical connections, 

 

 

●  check the mounting of the motor and fan,  whereby mind if the clearance between the impel- 

ler and  the non-rotary elements is equalised in the whole circumference, 

 

 

●  remove the impurities (eventually) deposited inside the fan. 

 
Prior to the re-start of the fan

 carry out the revision steps as listed in the Section 6

 

“Assembly

 

and Start-

up” of the present Use and Maintenance Manual. 

 

Exemption from this  are tests that

 need 

to be carried out on the

 device being in run, along  

with the strictly followed rules of Occupational Health and Safety 

 

as an example 

– mea

suring of vibrations. 

 

During the revision activities

  

it is important to follow the safety regulations. 

 

10.

 

Occupational Health and Safety 

Start up and the operational use of the fan  are admissible  after getting acquainted with 
the contents of the present Use and Maintenance Manual.   

The fan will not cause any

 mechanical hazard when it is correctly and firmly mounted

 to the roof

 

base

  

or another constructional element

 of the building  that has adequate load carrying capacity.  

 

 

Summary of Contents for SMART-EC-1300

Page 1: ...1 25 01 2019 Roof Fans SMART EC 1300 Use and Maintenance Manual Roof Fans SMART EC 1300 ...

Page 2: ...servations of Producer 4 4 Technical Data 4 5 Structure and Function 5 6 Assembly and Start up 6 7 Operational Use 8 8 Troubleshooting Guide 9 9 Maintenance 9 10 Occupational Health and Safety 9 11 Transport and Storage 10 12 Terms of warranty 10 13 Sample of the Declaration of Conformity 11 ...

Page 3: ...ates relating to the making available on the market of electrical equipment designed for use within certain voltage limits Journal of Laws EC L96 of 29 03 2014 The appliance meets the requirements included in 2009 125 EC ErP Directive of the European Parliament and of the Council of October 21th 2009 establishing a framework for the setting of ecodesign requirements for energy related pro ducts Jo...

Page 4: ...ng structure in pla ces where the roof fan shall be installed Unsure mounting could cause damage of the de vice risk to personnel people in the vicinity F SMART EC 1300 fan is not appropriate for conveying the air polluted with a mixture of flammable substances in a form of gas vapour mist or dust that could create the explosive atmosphere G Don t use the fan for conveying the air containing visco...

Page 5: ...pro tection against atmospheric conditions Under the cylindrical housing is located the fan inlet with a flange as a connection to the roof base Manufacturer suggests installing on sound absorbing roof bases type TPD or TPDC eventu ally on standard roof bases BI or BII On demand of Customer additionally can be installed rotational speed governors type RP for step less adjustment of the fans Struct...

Page 6: ...ded to install them on roof bases or wall brackets delivery on separate order To reduce the noise level it is advised to apply sound absorbing roof bases After the fan is placed on a roof base it is important to screw up thoroughly all the mounting bolts between the fan con nection and the roof base In the Fig No 2 are given the dimensions of the mounting flange and sound absorbing roof bases ...

Page 7: ...ate order Isolating switch ought to be installed by User on one s own in a place convenient for operator The way of connection is illustrated in Fig No 3 First take off the fan hood to get access to the terminal box of the fan motor After the connec tions are carried out install the hood It is important to select the suitable sort and section of the supply cable and appropriate protec tion against...

Page 8: ...urpose see Section 2 of the present Use and Maintenance Manual and when the reservations of manufacturer are not observed see Section 3 of the Use and Mainte nance Manual Consequences of improper use breakage of bearings balance loss of the rotary elements vibrations deformations damages caused by friction In case when any defective device function is noticed increased noise level vibrations reduc...

Page 9: ... use the isolating switch IS which should be ordered and installed by User Isolating switch ought to be installed within reach of the servicer Isolating switches IS are offered by KLIMAWENT S A as additional accessory The way of con nection is shown in the operation manual of the insolating switch IS There are subsequent activities within the range of technical revision examine and tighten up the ...

Page 10: ... weights placed on the package surface During loading reloading and transport the device should be neither thrown nor knocked down Do not put any additional load on the package It is inadmissible to put one device on top of another stacking During the transport protect them from atmospheric factors and from mechanical damage The fan must be stored in dry rooms and of efficient ventilation 12 Terms...

Page 11: ...oducts Journal of Laws L 285 of 31 10 2009 327 2011 EU Guideline of March 30th 2011 on implementing the 2009 125 EC Directive of the European Parlia ment and of the Council with regard to ecodesign requirements for fans driven by motors with an electric input po wer between 125W and 500 kW Journal of Laws L No 90 of 06 04 2011 The device has been constructed and produced on the basis of following ...

Page 12: ...ns SMART EC 1300 25 01 2019 Producer KLIMAWENT S A 81 571 Gdynia ul Chwaszczyńska 194 tel 058 629 64 80 fax 058 629 64 19 e mail klimawent klimawent com pl www klimawent com pl 812W80 SMART EC 1300 25 01 2019 EN ...

Reviews: