In case of every repair  or  spare part replacement  (according to 2014/34/EC 
ATEX Directive) it is important to apply an adequate information on an addi-
tional plate or in the enclosed documentation (a register log of repair activi- 
ties, etc.).  This is the duty of User!

 

Typical disturbances and their reasons are exposed below. 
 

8.

 

Troubleshooting Guide 

Table No.2 

 

Problem 

Possible reason 

Corrective action  

1

.  sudden vibrations of the  

hindrance objects, pollutants 

spot the barrier object /   

 

fan are occurring 

reducing the air flow got stack  pollutant and remove it 

 

 

in the duct or in the inlet 

 

 

 

the impeller is damaged 

replace the impeller with 

 

 

 

motor for new 

2

.  the fan does not start 

fade of one of the phases  or 

adjust the correct voltage 

 

 

the supply voltage is too low 

 

 

 

the block of protection activa-  make correct settings of the 

 

 

ted 

protections 

 

9.

 

Maintenance 

Construction of the fan  guarantees its longevity  and  reliable function without the constant  
routine technical supervision. 
To obtain correct functional performances and to meet the safety rules, 

it is

 

recommended 

submit the fan to technical revision in regular periods of time

.

 

 

 

Technical revisions on the fan must be executed by a qualified person with 
adequate authorization.  Additionally, the fan necessarily should by discon-
nected from the power supply system. 

 
During the technical revisions, follow the recommendations and instructions included  
in the User’s Manual of the motor,  that constitute integral part  of the main User’s Ma- 
nual of the fan. 

 

Before any revision activities on the fan, follow subsequent steps

 

disconnect the fan from the power supply system. Exclusion from it 

 

 

 

   are activities that must be carried out on the running fan, i.e. vibration

 

 

   measurements.  Whereby, observe strictly the Occupational and Health

 

 

   Safety regulations

 

 

 

wait until the impeller stops its rotations

 

 

 
Within the scope of technical revision carry out following steps

  examine and tighten up the mechanical- and electrical connections;  moreover check if any 

malfunctions are by noise or visually perceptible  

–  if this is the case, undertake its control. 

  undertake the inspection of the fan  (radial impeller of the fan motor  

–  according to the in- 

structions of the manufacturer).  During the technical inspection, clean the fan from deposi- 
ted impurities. 

 

Restart of the fan is possible, after the control steps as described in 

Section 6 “Assembly and 

Start-

up”. 

 

 

Summary of Contents for WP-11/Ex

Page 1: ...2 Application 3 3 Reservations of Producer 3 4 Technical Data 4 5 Structure and Function 5 6 Assembly and Start up 5 7 Operational Use 8 8 Troubleshooting Guide 9 9 Maintenance 9 10 Occupational Healt...

Page 2: ...of February 26th 2014 on the harmonisation of the laws of Member States relating to equipment and protective systems intended for use in potentially explosive atmospheres Journal of Laws EC L96 of 29...

Page 3: ...factories in areas of explosion hazard but this cannot be methane firedamp hazard neither carbon dust occurrence category 2 the device is designed for application in areas where explosive atmosphe re...

Page 4: ...eed the nominal rotations I Manufacturer is not responsible for wounds injuries body laceration experienced by User or personnel during the improper operational use 4 Technical Data Table No 1 Type Ro...

Page 5: ...ckage check the state of the fan if there are no damages that occurred during the transport WP 11 Ex duct fans are installed inside the rooms indoor application in vertical and horizontal round rigid...

Page 6: ...lations of Occupational and Health Safety and with the instructions given in Fig No4 CAUTION The fan is equipped with protective cables that should be connected to the ventila tion ducts Additionally...

Page 7: ...nnection and the target connection of the motor windings should be performed by investor too S1 isolating switch in Ex execution It is suggested to install the isolating switch in a place near the fan...

Page 8: ...tor Following use of the fan is treated as incorrect a conveying the aggressive media b forwarding the media of high dustiness or contaminant particles content c use of the fan in area where the ambie...

Page 9: ...it the fan to technical revision in regular periods of time Technical revisions on the fan must be executed by a qualified person with adequate authorization Additionally the fan necessarily should by...

Page 10: ...se garment clothing or putting the hand towards the open inlet of the running fan can cause hazard of accident and severe disabi lity 11 Transport and Storage WP 11 Ex ought to be wrapped in foil and...

Page 11: ...Electrical equipment of machines Part 1 Gene ral requirements EN ISO 13857 2010 Safety of machinery Safe distances to prevent hazard zones from be ing reached by upper and lower limbs EN 80079 0 2013...

Page 12: ...12 explosion proof duct fan WP 11 Ex 04 06 2019 NOTES...

Reviews: