04.06.2019                                

explosion-proof duct fan

  WP-11/Ex  

 

 
 

2.

 

Application 

Duct fans are designed  for general ventilation of the rooms,  where explosive 

atmosphere, (i.e. 

mixture of flammable substances in form of gas and vapour with the air, whereby after their  
ignition 

– in atmospheric conditions

  

– the burning mass would expand within the whole non-

burning mixture)

  

is likely to occur.

 

the whole non-burning mixture)

  

is likely to occur.   

The appliances are meant for installing inside the rooms (indoor application), directly in the 
system  of round ventilation ducts.  They have been constructed  for application within tem- 
perature range  -20 up to 40

C.   

The forwarded air must be of dustiness not exceeding 0,3 g/m

3

, without viscous pollutants and 

without aggressive compounds, and maximum temperature 6

0

C.  

 

According to

 

the 1914/34/EC ATEX Directive and

 

EN ISO 80079-36 the

 device carries the level  

of protection: 

HIGH

” – as a device classified for

 

Group

 II

,

 

Category

 2

,

 

and it can work in areas

 

where explosive atmospheres  are likely to occur.  

The fan

 can be applied in zones 

1

2

 (

G

). 

Specification of the operational zones and the knowledge on hazards caused by atmo- 
sphere of explosion risk in those zones 

– belongs to operator of the appliance. 

 The appliance is marked on the nominal data plate: 

 

II 2 G c Ex eb IIB T3

 

Marking

  

of

  

the

  

operational

  

conditions

  

of

  

the device

:

  group / category / hazard / class

.

 

 

 

  marking for explosion proof properties of the appliance, 

  group II

  

– the device

  

is

  

designed

  

for

  

on-ground work,

 

 

in factories,

  

in areas

  

of

  

explosion 

hazard,  

but this cannot be methane 

(

firedamp

)

 

hazard

 

neither carbon dust occurrence, 

  category 2

 

– the device is designed

  

for application in areas  where 

explosive atmosphe- 

res are likely to occur

  gas hazard G

 

c

” – category of protection against the ignition – 

constructional protection

  Ex

 

– mark of the electrical device – 

constructed

 

and

 tested according 

to the European Stan-

 

dards for work in areas of explosion hazard, 

  execution

 

e

” – type of construction of the motor (a motor of increased safety) 

 

b

” – protection by means of controlling the ignition sources,

 

 

gas explosion 

group

 IIB

 

– 

occurring

 in on-ground factories 

– the fans are constructed accor- 

ding to 

the PN-EN 14986:2009

, whereby they can be applied for gases in explosion groups 

IIA

 and 

IIB

 and 

hydrogen

 

temperature

 class T3

 

 the surface

 temperature 

of any

 part 

of the

 appliance should 

not

 

ex-

ceed 

200ºC

 (during the normal operation).  The device can be used safely

  

in explosive at-

mospheres

  

belonging to temperature classes 

T1

T2

T3

 

 

3.

 

Reservations of Producer 

A

.

 

Manufacturer accepts no liability

  

for any consequences following from the operational use 

that is in contradiction to the purpose of application. 

B

.

 

Installing of

 any additional elements not belonging to the normal device structure (

or acces

sory set) is not acceptable. 

C

.

 

Do not undertake

  

any structural changes  or constructional modifications on the device on 

one

’s own. 

D

.

 

Protect the appliance’s housing from mechanical damage. 

E

.

 

Prior to

 

installing

 check the load carrying capacity 

of the building structure

  

where the device  

will be mounted.  Unsure mounting could cause hazard to personnel/people in vicinity and  
effect in damage of the device. 

 
 

 

Summary of Contents for WP-11/Ex

Page 1: ...2 Application 3 3 Reservations of Producer 3 4 Technical Data 4 5 Structure and Function 5 6 Assembly and Start up 5 7 Operational Use 8 8 Troubleshooting Guide 9 9 Maintenance 9 10 Occupational Healt...

Page 2: ...of February 26th 2014 on the harmonisation of the laws of Member States relating to equipment and protective systems intended for use in potentially explosive atmospheres Journal of Laws EC L96 of 29...

Page 3: ...factories in areas of explosion hazard but this cannot be methane firedamp hazard neither carbon dust occurrence category 2 the device is designed for application in areas where explosive atmosphe re...

Page 4: ...eed the nominal rotations I Manufacturer is not responsible for wounds injuries body laceration experienced by User or personnel during the improper operational use 4 Technical Data Table No 1 Type Ro...

Page 5: ...ckage check the state of the fan if there are no damages that occurred during the transport WP 11 Ex duct fans are installed inside the rooms indoor application in vertical and horizontal round rigid...

Page 6: ...lations of Occupational and Health Safety and with the instructions given in Fig No4 CAUTION The fan is equipped with protective cables that should be connected to the ventila tion ducts Additionally...

Page 7: ...nnection and the target connection of the motor windings should be performed by investor too S1 isolating switch in Ex execution It is suggested to install the isolating switch in a place near the fan...

Page 8: ...tor Following use of the fan is treated as incorrect a conveying the aggressive media b forwarding the media of high dustiness or contaminant particles content c use of the fan in area where the ambie...

Page 9: ...it the fan to technical revision in regular periods of time Technical revisions on the fan must be executed by a qualified person with adequate authorization Additionally the fan necessarily should by...

Page 10: ...se garment clothing or putting the hand towards the open inlet of the running fan can cause hazard of accident and severe disabi lity 11 Transport and Storage WP 11 Ex ought to be wrapped in foil and...

Page 11: ...Electrical equipment of machines Part 1 Gene ral requirements EN ISO 13857 2010 Safety of machinery Safe distances to prevent hazard zones from be ing reached by upper and lower limbs EN 80079 0 2013...

Page 12: ...12 explosion proof duct fan WP 11 Ex 04 06 2019 NOTES...

Reviews: