background image

 

12 

                                                   

Fan chamber

  WPA-BOX-14                                      13.10.2016 

 

 

 

 

7.

 

Operational Use 

The construction do not require any additional maintenance after the start-up.  If the place of 
operational use is changed 

– repeat the steps as mentioned in Section 6

,

  

according to the in-

stalling and adapting the ventilation system to the new conditions. 
In case when any defective function of the unit occurs (e.g. improper noises or the outlook of 
the device)  follow steps as in Section 8. 

 
 

 

 

8.

 

Troubleshooting Guide 

Table No.6 

 

Problem 

  Possible reason 

 Corrective action  

1

Sudden and significant 

  Pollutants, foreign objects (being   Remove the pollutants; 

 

drop in intake volume flow. 

  obstacle do the air flow) have 

 clean the ventilation conduits. 

 

 

  deposited at the inlet grill. 

  

2

Sudden vibrations of the fan    Obstacle objects reducing  

 Disconnect the fan from 

 

are occurring. 

  the air flow got stack at the  

 the power supply system, 

 

 

  impeller. 

 and remove the obstacle. 

 

 

  The impeller is defective. 

 Replace the impeller with  

 

 

   

 motor for a new one. 

3

Noisy work of the fan 

  Incorrect impeller rotation sense.   Change the impeller rotation  

 

along with small volume flow.     

 sense by changing the phase 

 

 

   

 connection sequence  

 

 

   

  

 

 

 

9.

 

Maintenance 

In the aspect of operational use, the fan construction guarantees its efficient function without 
continuous routing 

everyday

 technical supervision. Nevertheless, to obtain proper function of  

the device 

and to follow the safety rules

manufacturer suggests execution of technical re- 

visions on regular basis

.  During the inspection check the function 

of the fan 

and the techni- 

cal state of its elements. 

 

 

 All the activity connected with

 power supply ought to be carried out by 

an authorized person with testified electrical qualifications. The appliance ought to be 
disconnected from the power supply system during that time. 

(

the exemption from this are 

activities

 carried out 

on the running fan, under strict

 obser- 

ving the Occupational and Health Safety rules 

– e.g. vibration  measurement

). 

Before the maintenance on the fan, necessarily disconnect it from the power supply system 
and wait until the impeller stops its rotations. 
 

Within the scope of inspection execute following activities

● 

check and tighten the mechanical and electrical connections, 

● 

examine the mountings of the motor and the fan,  important is that the clearance between  
the inlet and the impeller is even within the whole circumference. 

● 

remove the impurities accumulated inside the fan,  eventually clean it from pollutants  
originating from the conveyed medium. 

 
During the maintenance activities follow strictly the rules of Occupational Health and Safety, 
in order not to cause hazard to workers / people in the vicinity. 
 

 

Summary of Contents for WPA-BOX-14

Page 1: ...1 13 10 2016 Fan chamber WPA BOX 14 Use and Maintenance Manual Fan chamber WPA BOX 14...

Page 2: ...ations of Producer 4 4 Technical Data 4 5 Structure and Function 8 6 Assembly and Start up 10 7 Operational Use 12 8 Troubleshooting Guide 12 9 Maintenance 12 10 Occupational Health and Safety 13 11 T...

Page 3: ...ing to the making available on the market of electrical equipment designed for use within certain voltage limits Journal of Laws EC L96 of 29 03 2014 The appliance meets the requirements included in 2...

Page 4: ...tion with the air create explosive atmosphere F Do not use the device for conveying the air containing viscous impurities that could accumulate build up on the device surface especially on the impelle...

Page 5: ...5 13 10 2016 Fan chamber WPA BOX 14 Fig No 1 Dimensions of the fan chamber WPA BOX 14 Caution The dimension H is pertaining to holes spacing 10 used for anchorage the chamber...

Page 6: ...ensions of the fan chamber Type A mm B mm C mm Connection diameters Pitch diameters of the connections H mm J mm K mm D mm E mm F mm G mm WPA BOX 14 1641 1605 1666 400 400 430 430 766 M8 M8 Flow chart...

Page 7: ...kW see Table No 1 flow efficiency and pressure in the energy efficiency optimisation point see Table No 3 8 Rotations per minute see Table No 1 9 After the period of operational use follow steps acco...

Page 8: ...the floor and it is selec ted according to the weight of the fan stand frame set The fan inlet is equipped with a flange whereas the outlet is secured with a round fitting piece for attachment of the...

Page 9: ...degree Fan chamber with a silencer and air discharge at the silencer outlet Fan chamber with silencers at the inlet and outlet Photo No 1 Examples of application of additional silencers ADDITIONAL EQU...

Page 10: ...l power system has to be executed by User on one s own On the other hand it is important to select the right type and section of the supply cable and choose the appro priate short circuit and overload...

Page 11: ...h Q1 It 1 1 x In where In means rated current of the motor S1 isolating switch It is suggested to install it near the fan Purchase and installing depends on the Investor Connect the motor windings acc...

Page 12: ...tees its efficient function without continuous routing everyday technical supervision Nevertheless to obtain proper function of the device and to follow the safety rules manufacturer suggests executio...

Page 13: ...s this could cause the face injury of User 11 Transport and Storage The fan chamber is transported on a pallet The device has to be firmly fastened to the pallet to protect it from being overturned or...

Page 14: ...L 285 of 31 10 2009 327 2011 EU Guideline of March 30th 2011 on implementing the 2009 125 EC Directive of the European Parliament and of the Council with regard to ecodesign requirements for fans dri...

Page 15: ...15 13 10 2016 Fan chamber WPA BOX 14 NOTES...

Page 16: ...amber WPA BOX 14 13 10 2016 Producer KLIMAWENT S A 81 571 Gdynia ul Chwaszczy ska 194 tel 058 629 64 80 fax 058 629 64 19 e mail klimawent klimawent com pl www klimawent com pl 814K49 WPA BOX 14 13 10...

Reviews:

Related manuals for WPA-BOX-14