AUTOMATION AND CONTROL SYSTEM FOR UNITS
EVO-T; EVO-T COMPACT
OPERATION AND MAINTENANCE MANUAL
2. EXECUTION STANDARD
2.1 Characteristics of the standard EVO-T and EVO-T COMPACT
control system:
• Wall-mounted Danfoss inverters installed near EVO-T con-
trol cabinet
• Plastic EVO-T control cabinet, IP40-rated – internal version
• In the EVO-T COMPACT, the supply temperature sensor is de-
livered in bulk with an additional cable of 10 m.
Fig. 2
Supply temperature sensor
Table No. 1
Electric parameters of EVO-T (COMPACT) Control Cabinets
NAME
„2S”
„4S”
Rated voltage (Un)
400V, 50Hz
Insulation rated voltage (Ui)
500V
Rated surge with stand voltage (Uimp)
4kV
Assembly rated current (InA)
KLIMOR_DTR_EVO-T_E.SCH_060.x.x
Circuit rated current (InC)
KLIMOR_DTR_EVO-T_E.SCH_060.x.x
Rated short-duration with stand current (Icw)
1,5 kA
Coordination of short-circuit protections
KLIMOR_DTR_EVO-T_E.SCH_060.x.x
Rated frequency (fn)
50Hz
Type of the grounding system
TN-S
Version
internal
Protection class
IP 40
EMC classification
Environment 2 [class A]
External impact protection
IK05
Contamination level
3
Operating conditions
10°C ÷ +40°C, (daily average 24h< +35°C)
Dimensions
406x303x98 mm
406x303x98 mm
Weight
3,3 kg
3,6 kg
2.2 Functions performed by control cabinet
• Power supply and control with the Modbus RS485 of the AC
(only in EVO-T) motor inverters or EC motor
• Power supply and control of rotational recovery (1×230VAC)
• Power supply and control of the water heating coil circula-
tion pump (1x230VAC)
• The control system’s controller
• Control of the electric heater (start/stop signal, 0÷10VDC
signal and return alarm signal), the electric heater must be
equipped with its own power supply and control system
(can be control the electrical heater through output
Aout1 as a PWM 0-10VDC, the choice we make in the ser-
vice Menu/Configuration/Electric heater)
• Control of DX cooler (start/stop signal, 0-10VDC or 1,2
stage), the cooler has to be equipped with its own power
supply and control system
• For the DX unit it is possible to choose the type of exchang-
er from: cooling DX exchanger or DX reverse exchanger
cooling and heating.
• For water cooler control systems (without water and elec-
tric heater) it is possible to activate the H/C water exchang-
er, it is a heater and cooler implemented physically through
one exchanger with one set of actuator and circulating
pump, switching the heating and cooling mode occurs au-
tomatically from the settings of the season and the external
temperature sensor
• UV lamp control
• Electrostatic filter control
• 24VAC power supply and control of supply, exhaust, recir-
culation and cross-recovery dampers.
• 24VAC power supply and control of valve actuators for
heaters and water coolers
3. CONTROL CABINET CODING
Table No. 2
Control cabinet sizes
Index
Name
Internal version – pla-
stic IP40-rated [HxWxD]
99000521027363
CG_EVO-T-2S – Compact
303x407x98 mm
99000521027364
CG_EVO-T-4S – Compact
303x407x98 mm
99000521027329
CG_EVO-T-2S – HMI Touch 4,3”
303x407x98 mm
99000521027330
CG_EVO-T-4S – HMI Touch 4,3”
303x407x98 mm
99000521027365
CG_EVO-T-2S – HMI Touch 7”
303x407x98 mm
99000521027366
CG_EVO-T-4S – HMI Touch 7”
303x407x98 mm
Summary of Contents for EVO-T COMPACT
Page 13: ...11 NOTATKI...
Page 14: ...SERWIS SERVICE 48 587839954 48 500087227 serwis klimor com...
Page 25: ...23 NOTES...
Page 26: ...SERWIS SERVICE 48 587839954 48 500087227 serwis klimor com...
Page 27: ...A Y EVO T EVO T COMPACT KLIMOR EVO T_CS...
Page 31: ...29 4 3 1 2 1 2 DX 1 2 13 C 1 2 1 C 1 2 30...
Page 35: ...33 7...
Page 36: ...34 EVO T EVO T COMPACT...
Page 37: ......