20
AUTOMATION AND CONTROL SYSTEM FOR UNITS
EVO-T; EVO-T COMPACT
OPERATION AND MAINTENANCE MANUAL
6.2 Communication RS485 Slave, Modbus RTU and connection
method with the EC motor
Fig. 5
Example for double air supply, double air exhaust
Fig. 21.
Example for single air supply, single air exhaust.
Table No. 7
Connection of the EBM fan wires (EC motor)
Cable
Connection
Cable color
Cable function
1,2
PE
yellow-green
Ground
3
N
Blue
Power supply – "0"
5
L
Black
Power supply – Phase
6
NC
White 1
Motor condition relay – open, failure
7
COM
White 2
Motor condition relay – open, failure
8
0-10V
Yellow
Analog input
10
RSB
Brown
RS485 MODBUS
11
RSA
White
RS 485 MODBUS
12
GND
Blue
"0" for control signal
13
+10V
Red
10VDC 10mA output
Only 1, 2, 3, 5, 6, 7, 10, 11, 12 wires are connected to appropriate terminals at
the control board.