Operating instructions Type INTEC / KH2F-CI 

page 

4

 of 

7

 

           Valid from 01/2018 

 

 

 

5  Installation 

5.1    Generals 

With the help of a method of a pipe installation which is usual in the trade, the ball valves can be installed 
at any position. Please take care that the ball valves are accessible for the operation. 
The flow direction is arbitrary (with exception of the variants with relief well). The ball valves can also be 
installed by changing the direction of the flow. Ball valves with specified flow direction have an indication 
via a direction sign. 
Valves and pipes which are operated at high (> 50°C) or deep (< 0 °C) temperatures must be protected 
from touch by an insulation, or corresponding warning plates must show the danger of touch. 
For melting water or danger of icing in air conditioning plants, cooling- and refrigerating plants, a special 
and diffusion tight insulation of the complete valve possibly including the hand lever is necessary. If the 
ball valve gets covered by ice, there is the danger that the valve can not be operated anymore. Special 
types for low temperatures must be required in the inquiries. 

 

If a ball valve is installed in the pipe as an end valve, the valve must be safeguarded with 
suitable measures against unauthorized or unintended opening, as there is danger of injury 
when closing the valve and damage or injury to persons shall be avoided. 
During the installation no static or dynamic power may affect the ball valves. The ball valves 

may not be used as a fixed point of the pipe. Harmful tie force, force of pressure of lateral power must be 
kept away from the valves to avoid leakages and break of the body. The plastic caps have to be removed 
shortly  before  the  installation  of  the  ball  valves.  The  pipe  must  be  washed  to  remove  dirt,  forge,  wire  
edges, zinc- and welding residues, since otherwise the ball or the sealing can be damaged.

 

 

 

5.1.1

 

Ball valves with flange connection 

During the  installation one must keep a special eye  on the  parallelism of the pipe flange  as 
well  as  on  an  exact  snug  fit.  Only  suitable  screws,  nuts  and  sealing  should  be  used.  
If necessary, current installation notes as well as media- and temperature compatibility have 
to be taken into consideration when the sealings will be installed. The sealings must be well 
centred. The screws must be tightened crosswise with specified torque  

 
5.1.2

 

Ball valves with threaded ends 

Connection  according  to  EN  10226-1:  The  connection  to  the  pipe  will  be  achieved  by  a  cylindrical  
Whitworth-female thread according to EN 10226-1. It is a system at which the sealing is in the thread of 
the pipe thread. Fittings or pipes  with  a tapered male thread and  a suitable sealing shall  be used as  a 
counterpart.  

 

Connection according to EN ISO 228-1: The threaded joints have a cylindrical Whitworth-female thread 
according to EN ISO 228-1. This is a system at which the sealing is not in the thread of the pipe thread. 
Fittings  or  pipes  with  a  cylindrical male  thread  and  a  sealing  are  required  as  counterparts.  The  sealing 
has to be installed between the bearing surface of the flange sleeve and the plain fore part of the counter 
part and must be pressed. The sealing surface must be metallically clean and dry. Suitable sealings have 
to be used (please follow the media- and temperature compatibility) and the applicable installation notes 
have to be taken into account. 

     

The  body  of  the  ball  valves  has  a  mounted  hexagon  on  both  sides.  Because  of  that,  the  ball 

             valves must be kept in the required installation position with a suitable tool and the screwing force 
            can be reversed laterally. 

 

Summary of Contents for INTEC Series

Page 1: ... Working at valves 3 4 3 Staff 3 4 4 Notes for the operator 3 5 Installation 4 5 1 Generals 4 5 1 1 Ball valves with flange connection 4 5 1 2 Ball valves with threaded ends 4 5 1 3 Ball valves with welded ends 5 5 2 Valves with actuators 5 5 2 1 General notes 5 5 2 2 Functional testing 5 6 Operation 5 7 Storage and transport 6 8 Maintenance 6 9 Stopping and dismantling of ball valves 6 9 1 Genera...

Page 2: ...atic or electric actuator Connection Possible connections of ball valves flange connection threaded ends or welded ends see also the respective data sheet Special design Please use a special design at danger of an electrical charging at contact with oxygen on request of the leakage inspection at freezing danger at fire risk or at increased temperature requests 4 Safety 4 1 Safety notes The non com...

Page 3: ...t Operating error of a valve can lead to emphatic consequences e g o outflow of the medium o machine plant down time o impairment decrease increase of the effect function of the plant machine o fail of important functions of the valve plant o fail of specified methods for maintenance o endangering of persons because of thermal electric mechanical and chemical influences o endangering of the enviro...

Page 4: ...e the installation of the ball valves The pipe must be washed to remove dirt forge wire edges zinc and welding residues since otherwise the ball or the sealing can be damaged 5 1 1 Ball valves with flange connection During the installation one must keep a special eye on the parallelism of the pipe flange as well as on an exact snug fit Only suitable screws nuts and sealing should be used If necess...

Page 5: ...ional testing 5 2 Valves with actuators 5 2 1 General notes The connection of electrical cable may only be carried out by trained staff The regulations according to VDE 0100 and VDE 0165 explosion proofness must be taken into consideration All electrical equipment like actuator switch box solenoid valve limit switches etc must be installed safe against flooding in dry rooms Voltage and frequency m...

Page 6: ...mended attention Not for the oxygen type Afterwards the ball valves should be opened and closed at least twice Ball valves with single acting actuators with safety position fail safe closed can be delivered in closed position If necessary the valve must be cleaned before the assembly Special actuated valves with mounted solenoid valves and limit switches must be handled with special care It is rec...

Page 7: ... of contamination 9 2 Actuators If actuators supplied with bulk supply must be dismantled from the valves or even dismantled itself the bulk supply must be switched off before starting with the work and the notes of the operating instruction of the actuator must be taken into account 10 Inspection Abrasion can damage the sealing For that reason the tightness of the ball valve must be checked regul...

Reviews: