Specifications
4
Outputs, Single-stage triac
1
Key features
Optically isolated triac output.
Programmable a binary object.
Connector
Removable screw terminal block
Wire size 14-22 AWG
Output range
Maximum switching 30 volts AC at 1 ampere
Outputs, Dual-stage triac
2
Key features
Optically isolated triac output.
Programmable as binary object.
Connector
Removable screw terminal block
Wire size 14-22 AWG
Output range
Maximum switching 30 volts AC at 1 ampere
Communications
BACnet MS/TP
EIA–485 operating at rates up to 76.8 kilobaud.
Automatic baud detection.
Automatically assigns MAC addresses and device
instance numbers.
Removable screw terminal block.
Wire size 14–22 AWG
NetSensor
Compatible with models KMD–1161 and KMD–1181,
Connects through RJ–12 connector.
Programmable features
Control Basic
10 program areas
PID loop objects
4 loop objects
Value objects
40 analog and 40 binary
Time keeping
Real time clock with power backup for 72 hours
(BAC-7302-C only)
See PIC statement for supported BACnet objects
Schedules
Schedule objects
8
Calendar objects
3
Trend objects
8 objects each of which holds 256 samples
Alarms and events
Intrinsic reporting
Supported for input, output, value, accumulator,
trend and loop objects.
Notification class objects
8
Memory
Programs and program parameters are stored in
nonvolatile memory.
Auto restart on power failure