BAC-9000 Series Controller Installation Guide 

4 921-019-01F

18

19

CONNECT (OPT.) ETHERNET NETWORK

1.  For a BAC-9001C

E

 (only), connect an 

Ethernet 

patch cable

 

20

 to the 

10/100 ETHERNET

 

port.

   CAUTION 

On Conquest “E” models, do NOT 

plug a cable meant for Ethernet 

communications into the Room Sensor 

port! The Room Sensor port powers a 

NetSensor, and the supplied voltage 

may damage an Ethernet switch or 

router.

NOTE: 

Before May 2016, BAC-9001CE models 

had a 

single

 Ethernet port 

20

. They 

now have 

dual

 Ethernet ports 

21

enabling daisy-chaining of controllers. 

See the 

Daisy-Chaining Conquest 

Ethernet Controllers Technical 

Bulletin 

on the 

KMC Partner web site

 

for more information.

20

NOTE: 

No more than two (16 AWG) wires can 

be joined at a common point.

17

CONNECT (OPTIONAL) PRESSURE SENSOR

NOTE: 

Complete the steps in this section 

to connect an air flow sensor to the 

controller.

NOTE: 

Only the BAC-9021 controller does not 

have PRESSURE SENSOR ports. For 

that model, skip this section.

NOTE: 

Use 1/4 inch (6.35 mm) FR tubing. 

Tubing should not be longer than 20 

feet (6 meters).

1.  Remove the 

black shipping plugs

 

16

 from the 

PRESSURE SENSOR ports.

2.  Connect the high pressure tube from the 

pressure flow sensor to the 

HIGH 

18

 port on 

the controller.

3.  Connect the low pressure tube from the 

pressure flow sensor to the 

LOW 

19

 port on 

the controller.

Summary of Contents for BAC-9001

Page 1: ...steps in this section if the VAV damper rotation limit is either 60 or 45 degrees NOTE If the VAV damper rotates 90 degrees skip this section and go to Mount Controller on page 2 instead 1 Push and hold the gear release 1 and rotate the drive hub and V clamp 2 to the left KMC Controls 19476 Industrial Drive New Paris IN 46553 877 444 5622 Fax 574 831 5252 www kmccontrols com CONTENTS Introduction ...

Page 2: ...ts and outputs The gray terminals if present are for MS TP communication 5 Finger tighten the V clamp nuts 11 to position the damper shaft in the drive hub 10 11 6 Center the mounting bushing 12 in the mounting tab 13 5 6 5 Tighten the screw until the screw head touches the plastic in the bottom of the recess NOTE Overtightening the screw can cause compression in the case which may interfere with ...

Page 3: ...se 24 VAC only with triac outputs BO6 BO9 with SC NOTE Wire sizes 12 24 AWG can be clamped in each terminal 12 13 7 Attach the controller to the VAV box with a 8 sheet metal screw through the mounting bushing 12 8 Evenly tighten the V clamp nuts 11 on the drive hub to 30 35 in lb CONNECT SENSORS AND EQUIPMENT NOTE A digital STE 9000 Series NetSensor can be used for configuring the controller see C...

Page 4: ...Chaining Conquest Ethernet Controllers Technical Bulletin on the KMC Partner web site for more information 20 NOTE No more than two 16 AWG wires can be joined at a common point 17 CONNECT OPTIONAL PRESSURE SENSOR NOTE Complete the steps in this section to connect an air flow sensor to the controller NOTE Only the BAC 9021 controller does not have PRESSURE SENSOR ports For that model skip this sect...

Page 5: ...tain RF emissions specifications NOTE Also on the newer models the Room Sensor port is yellow 22 instead of black to help differentiate it from the black Ethernet ports 22 21 NOTE The Ethernet patch cable should be T568B Category 5 or better and a maximum of 328 feet 100 meters between devices CONNECT OPTIONAL MS TP NETWORK 1 For a BAC 9001 or BAC 9021 connect the network to the gray BACnet MS TP ...

Page 6: ...eed The green Ethernet LED stays ON when the controller is communicating with the network The green Ethernet LED is OFF when the powered controller is not communicating with the network 30 31 Amber ETHERNET LED 31 The amber Ethernet LED flashes when the controller is communicating with a 100BaseT Ethernet network The amber Ethernet LED remains OFF when the powered controller is communicating with ...

Page 7: ...unning the KMC Connect Lite app Full configuration and programming of KMC Conquest controllers is supported starting with TotalControl ver 4 0 WATCH DOG JUMPER The watch dog jumper 33 resets the controller if there is a power failure or a communication timeout between the controller and the network Never remove the jumper from the two outer pins 33 CONFIGURE PROGRAM THE CONTROLLER See the table on...

Page 8: ...thernet patch cord NOTE Analog inputs accept 1K or 10K sensors 0 12 VDC or 4 20 mA NOTE For more wiring examples see the wiring diagrams that are part of the application library in KMC Connect Converge or TotalControl STE 9521 STE 6010 10 Single Duct VAV Series Fan Powered with Floating Reheat and Vent Control L H 1 4 6 35 FR tubing to flow sensor COM 24 VAC Only Phase Neutral Fan Start Fan Speed ...

Page 9: ...ising out of or related to the use of this document The KMC logo is a registered trademark of KMC Controls Inc All rights reserved TEL 574 831 5250 FAX 574 831 5252 EMAIL info kmccontrols com REPLACEMENT PARTS HPO 0055 Replacement Network Bulb Module for Conquest Controllers Pack of 5 HPO 9901 Conquest Hardware Replacement Parts Kit NOTE HPO 9901 includes the following Terminal Blocks DIN Clips 1 ...

Reviews: