background image

BAC-9000 Series Controller Installation Guide 

6 921-019-01F

POWER AND COMMUNICATION STATUS

The 

status LEDs

 indicate power connection and 

network communication. The descriptions below 

describe their activity during 

normal operation

 (at 

least 5 to 20 seconds 

after

 power-up/initialization 

or restart).

NOTE: 

If both the green READY LED and the 

amber COMM LED remain OFF, check 

the power and cable connections to the 

controller.

Green READY LED 

28

After controller power-up or restart is complete, 

the READY LED flashes steadily about once per 

second, indicating normal operation.

Amber (BACnet MS/TP) COMM LED 

29

During normal operation, the COMM LED 

flickers as the controller receives and passes 

the token over the BACnet MS/TP network.

When the network is 

not

 connected or 

communicating properly, the COMM LED 

flashes more slowly (about once a second).

28

29

Green ETHERNET LED 

30

NOTE: 

The Ethernet status LEDs 

indicate network connection and 

communication speed.

The green Ethernet LED stays ON when the 

controller is communicating with the network.

The green Ethernet LED is OFF when the 

(powered) controller is 

not

 communicating 

with the network.

30

31

Amber ETHERNET LED 

31

The amber Ethernet LED flashes when the 

controller is communicating with a 100BaseT 

Ethernet network.

The amber Ethernet LED remains OFF when 

the (powered) controller is communicating 

with the network at only 10 Mbps (instead of 

100 Mbps).

NOTE: 

If both the green and amber Ethernet 

LEDs remain OFF, check the power and 

network cable connections.

MS/TP NETWORK ISOLATION BULBS

32

The two 

network isolation bulbs

 

32

 serve three 

functions:

Removing the (

HPO-0055

) bulb assembly 

opens the MS/TP circuit and isolates the 

controller from the network.

If one or both bulbs are ON, the network is 

improperly phased. This means the ground 

potential of the controller is not the same 

as other controllers on the network. If 

this happens, fix the wiring. See 

Connect 

(Optional) MS/TP Network on page 5

.

If the voltage or current on the network 

exceeds safe levels, the bulbs blow, opening 

the circuit. If this happens, fix the problem and 

replace the bulb assembly.

Summary of Contents for BAC-9001

Page 1: ...steps in this section if the VAV damper rotation limit is either 60 or 45 degrees NOTE If the VAV damper rotates 90 degrees skip this section and go to Mount Controller on page 2 instead 1 Push and hold the gear release 1 and rotate the drive hub and V clamp 2 to the left KMC Controls 19476 Industrial Drive New Paris IN 46553 877 444 5622 Fax 574 831 5252 www kmccontrols com CONTENTS Introduction ...

Page 2: ...ts and outputs The gray terminals if present are for MS TP communication 5 Finger tighten the V clamp nuts 11 to position the damper shaft in the drive hub 10 11 6 Center the mounting bushing 12 in the mounting tab 13 5 6 5 Tighten the screw until the screw head touches the plastic in the bottom of the recess NOTE Overtightening the screw can cause compression in the case which may interfere with ...

Page 3: ...se 24 VAC only with triac outputs BO6 BO9 with SC NOTE Wire sizes 12 24 AWG can be clamped in each terminal 12 13 7 Attach the controller to the VAV box with a 8 sheet metal screw through the mounting bushing 12 8 Evenly tighten the V clamp nuts 11 on the drive hub to 30 35 in lb CONNECT SENSORS AND EQUIPMENT NOTE A digital STE 9000 Series NetSensor can be used for configuring the controller see C...

Page 4: ...Chaining Conquest Ethernet Controllers Technical Bulletin on the KMC Partner web site for more information 20 NOTE No more than two 16 AWG wires can be joined at a common point 17 CONNECT OPTIONAL PRESSURE SENSOR NOTE Complete the steps in this section to connect an air flow sensor to the controller NOTE Only the BAC 9021 controller does not have PRESSURE SENSOR ports For that model skip this sect...

Page 5: ...tain RF emissions specifications NOTE Also on the newer models the Room Sensor port is yellow 22 instead of black to help differentiate it from the black Ethernet ports 22 21 NOTE The Ethernet patch cable should be T568B Category 5 or better and a maximum of 328 feet 100 meters between devices CONNECT OPTIONAL MS TP NETWORK 1 For a BAC 9001 or BAC 9021 connect the network to the gray BACnet MS TP ...

Page 6: ...eed The green Ethernet LED stays ON when the controller is communicating with the network The green Ethernet LED is OFF when the powered controller is not communicating with the network 30 31 Amber ETHERNET LED 31 The amber Ethernet LED flashes when the controller is communicating with a 100BaseT Ethernet network The amber Ethernet LED remains OFF when the powered controller is communicating with ...

Page 7: ...unning the KMC Connect Lite app Full configuration and programming of KMC Conquest controllers is supported starting with TotalControl ver 4 0 WATCH DOG JUMPER The watch dog jumper 33 resets the controller if there is a power failure or a communication timeout between the controller and the network Never remove the jumper from the two outer pins 33 CONFIGURE PROGRAM THE CONTROLLER See the table on...

Page 8: ...thernet patch cord NOTE Analog inputs accept 1K or 10K sensors 0 12 VDC or 4 20 mA NOTE For more wiring examples see the wiring diagrams that are part of the application library in KMC Connect Converge or TotalControl STE 9521 STE 6010 10 Single Duct VAV Series Fan Powered with Floating Reheat and Vent Control L H 1 4 6 35 FR tubing to flow sensor COM 24 VAC Only Phase Neutral Fan Start Fan Speed ...

Page 9: ...ising out of or related to the use of this document The KMC logo is a registered trademark of KMC Controls Inc All rights reserved TEL 574 831 5250 FAX 574 831 5252 EMAIL info kmccontrols com REPLACEMENT PARTS HPO 0055 Replacement Network Bulb Module for Conquest Controllers Pack of 5 HPO 9901 Conquest Hardware Replacement Parts Kit NOTE HPO 9901 includes the following Terminal Blocks DIN Clips 1 ...

Reviews: