background image

BAC-9300 Series Controller Installation Guide 

3 925-019-02G

CONNECT (OPT.) ETHERNET NETWORK

1.  For BAC-93x1C

E

 models (only), connect 

an 

Ethernet patch cable

 

14

 to the 

10/100 

ETHERNET

 port

 

(“E” models only).

   CAUTION 

On Conquest “E” models, do NOT 

plug a cable meant for Ethernet 

communications into the Room Sensor 

port! The Room Sensor port powers a 

NetSensor, and the supplied voltage 

may damage an Ethernet switch or 

router.

NOTE: 

The Ethernet patch cable should be 

T568B Category 5 or better and a 

maximum of 328 feet (100 meters) 

between devices.

NOTE: 

Before May 2016, BAC-xxxxCE models 

had a single Ethernet port. They now 

have dual Ethernet ports, enabling 

daisy-chaining of controllers 

14

. See 

the 

Daisy-Chaining Conquest Ethernet 

Controllers Technical Bulletin 

on 

the 

KMC Partner web site

 for more 

information.

NOTE: 

On newer models, the Room Sensor 

port is yellow 

8

 instead of black to 

help differentiate it from the black 

Ethernet ports.

NOTE: 

For more information, see 

Sample 

(BAC-9311) Wiring on page 7

 and the 

YouTube video 

KMC Conquest Wiring: 

BAC-9300 Series Unitary Controllers

.

14

   CAUTION 

Do 

NOT

 connect 24 VAC to the analog 

outputs (UO7–UO10 and GNDs)!

NOTE: 

Use 24 V

AC

 (only) with triac outputs 

(BO1–BO6 with SCs).

CONNECT (OPT.) PRESSURE FLOW SENSOR

NOTE: 

Complete the steps in this section to 

connect an air flow sensor to the BAC-

93

1

1/93

1

1C/93

1

1CE controller.

NOTE: 

BAC-93

0

1/93

0

1C/93

0

1CE controllers 

do 

not

 have PRESSURE SENSOR ports.

NOTE: 

Use 1/4 inch (6.35 mm) FR tubing. 

Tubing should not be longer than 6 feet 

(20 meters).

1. 

Remove the 

black shipping plugs

 

9

 from the 

PRESSURE SENSOR ports.

2.  Connect the high pressure tube from the 

pressure flow sensor to the 

HIGH 

12

 port on 

the controller.

3.  Connect the low pressure tube from the 

pressure flow sensor to the 

LOW

 

13

 port on 

the controller.

13

12

Summary of Contents for BAC-9300 Series

Page 1: ...formation see the KMC Conquest Controller Application Guide MOUNT CONTROLLER NOTE Mount the controller inside a metal enclosure for RF shielding and physical protection NOTE To mount the controller with screws on a flat surface complete the steps in On a Flat Surface on page 1 Or to mount the controller on a 35 mm DIN rail such as integrated in an HCO 1103 enclosure complete the steps in On a DIN ...

Page 2: ...relevant installation guide for additional details 7 1 Plug an Ethernet patch cable 7 connected to an STE 9000 Series or STE 6010 6014 6017 sensor into the yellow ROOM SENSOR port 8 of the controller NOTE The Ethernet patch cable should be a maximum of 150 feet 45 meters CAUTION On Conquest E models do NOT plug a cable meant for Ethernet communications into the Room Sensor port The Room Sensor por...

Page 3: ...nformation NOTE On newer models the Room Sensor port is yellow 8 instead of black to help differentiate it from the black Ethernet ports NOTE For more information see Sample BAC 9311 Wiring on page 7 and the YouTube video KMC Conquest Wiring BAC 9300 Series Unitary Controllers 14 CAUTION Do NOT connect 24 VAC to the analog outputs UO7 UO10 and GNDs NOTE Use 24 VAC only with triac outputs BO1 BO6 w...

Page 4: ... the amber COMM LED remain OFF check the power and cable connections to the controller CONNECT OPTIONAL MS TP NETWORK 1 For BAC 93x1 93x1C models only connect the BACnet network to the gray BACnet MS TP terminal block 15 15 NOTE Use 18 gauge AWG shielded twisted pair cable with maximum capacitance of 51 picofarads per foot 0 3 meters for all network wiring Belden cable 82760 or equivalent A Connec...

Page 5: ...etwork 22 21 Amber ETHERNET LED 22 The amber Ethernet LED flashes when the controller is communicating with a 100BaseT Ethernet network The amber Ethernet LED remains OFF when the powered controller is communicating with the network at only 10 Mbps instead of 100 Mbps NOTE If both the green and amber Ethernet LEDs remain OFF check the power and network cable connections MS TP NETWORK ISOLATION BUL...

Page 6: ...mate K factor from the chart in the Appendix K Factors for VAV section in the KMC Conquest Controller Application Guide For instructions on VAV balancing With an STE 9000 series NetSensor see the VAV Airflow Balancing with an STE 9xx1 section of the KMC Conquest Controller Application Guide With a BAC 5051E Router see its application and installation guide With KMC Connect or TotalControl see the ...

Page 7: ...E For Ethernet models connect the controller to the network with a standard Ethernet patch cord NOTE Analog inputs accept 1K or 10K sensors 0 12 VDC or 4 20 mA NOTE For more wiring examples see the wiring diagrams that are part of the application library in KMC Connect Converge or TotalControl Early models shown in the drawings had different terminal locations Follow the terminal labels not locati...

Page 8: ...ff BO5 Binary Heating Valve On Off BO6 Binary Output 6 BO6 Binary Output 6 AO7 and BO4 are controlled simultaneously AO8 and BO5 are controlled simultaneously AO7 and BO4 are controlled simultaneously AO8 and BO5 are controlled simultaneously BAC 9301 HPU BAC 9311 HPU Inputs Inputs AI1 Space Sensor on Room Sensor port AI1 Space Sensor on Room Sensor port AI2 Space Setpoint Offset on port AI2 Space...

Page 9: ...tage 2 BO3 Cool Stage 2 BO4 Binary Output 4 BO4 Binary Output 4 BO5 Heating Stage 1 BO5 Heating Stage 1 BO6 Heating Stage 2 BO6 Heating Stage 2 BAC 9311 VAV Inputs AI1 Space Sensor on Room Sensor port AI2 Space Setpoint Offset on port AI3 UI3 Discharge Air Temperature AI4 UI4 Analog Input 4 AI5 UI5 Analog Input 5 AI6 UI6 Analog Input 6 AI7 UI7 Analog Input 7 AI8 UI8 Primary Damper Position AI9 Pri...

Page 10: ...amages direct or incidental arising out of or related to the use of this document The KMC logo is a registered trademark of KMC Controls Inc All rights reserved TEL 574 831 5250 FAX 574 831 5252 EMAIL info kmccontrols com REPLACEMENT PARTS HPO 0055 Replacement Network Bulb Module for Conquest Controllers Pack of 5 HPO 9901 Conquest Hardware Replacement Parts Kit NOTE HPO 9901 includes the followin...