background image

BAC-9300 Series Controller Installation Guide 

6 925-019-02G

CONFIGURE/PROGRAM THE CONTROLLER

See the table for the most relevant KMC Controls 

tool for configuring, programming, and/or creating 

graphics for the controller. See the documents or 

Help systems for the respective KMC tool for more 

information.
See the table (on the next page) for the most 

relevant KMC Controls tools for configuring, 

programming, and/or creating graphics for the 

controller. See the tools’ documents or Help 

systems for more information.

NOTE: 

After the controller has been 

configured, an STE-6010/6014/6017 

series analog sensor can be connected 

to the controller in place of an STE-

9000 series digital NetSensor.

NOTE: 

A BAC-9301C

E

 can be configured by 

connecting an HTML5-compatible 

web browser to the controller’s default 

IP address (192.168.1.251). See 

the 

Conquest Ethernet Controller 

Configuration 

Web Pages Application 

Guide

 for more information about the 

built-in configuration web pages.

NOTE: 

To configure a VAV controller, enter 

the correct 

K factor

 for the VAV 

box. Typically, this is supplied by 

the manufacturer of the VAV unit. If 

this information is unavailable, use 

an approximate K factor from the 

chart in the Appendix: K Factors for 

VAV section in the 

KMC Conquest 

Controller Application Guide

.

For instructions on 

VAV balancing

:

With an 

STE-9000

 series NetSensor, see 

the VAV Airflow Balancing with an STE-9xx1 

section of the 

KMC Conquest Controller 

Application Guide

.

With a 

BAC-5051E Router

, see its 

application 

and installation guide

.

With 

KMC Connect

 or 

TotalControl

, see the 

Help system for the software.

SETUP PROCESS

KMC 

CONTROLS 

TOOL

Config

-

uration

Programming 

(Control Basic)

Web Page 

Graphics*

4

Conquest 

NetSensor

4

Internal con-

figuration web 

pages in Con-

quest Ethernet 

“E” models**

4

KMC Connect 

Lite

 (NFC) 

app***

4

4

KMC Con-

nect

 software

4

****

4

****

4

TotalControl

 

software

4

4

KMC Con-

verge

 module 

for Niagara 

WorkBench

4

KMC Con-

verge

 GFX

 

module for 

Niagara Work-

Bench

    *Custom graphical user-interface web pages can be 

       hosted on a remote web server, but not in the

 

       controller.
   **Conquest Ethernet-enabled “E” models with the 

       latest firmware can be configured with an HTML5

 

       compatible web browser from pages served from

 

       within the controller. For information, see the 

Con 

       quest Ethernet Controller Configuration Web

 

       Pages Application Guide

.

 ***Near Field Communication via enabled smart

 

       phone or tablet running the KMC Connect Lite app.

****Full configuration and programming of KMC

 

       Conquest controllers is supported starting with 

       TotalControl ver. 4.0.

Summary of Contents for BAC-9300 Series

Page 1: ...formation see the KMC Conquest Controller Application Guide MOUNT CONTROLLER NOTE Mount the controller inside a metal enclosure for RF shielding and physical protection NOTE To mount the controller with screws on a flat surface complete the steps in On a Flat Surface on page 1 Or to mount the controller on a 35 mm DIN rail such as integrated in an HCO 1103 enclosure complete the steps in On a DIN ...

Page 2: ...relevant installation guide for additional details 7 1 Plug an Ethernet patch cable 7 connected to an STE 9000 Series or STE 6010 6014 6017 sensor into the yellow ROOM SENSOR port 8 of the controller NOTE The Ethernet patch cable should be a maximum of 150 feet 45 meters CAUTION On Conquest E models do NOT plug a cable meant for Ethernet communications into the Room Sensor port The Room Sensor por...

Page 3: ...nformation NOTE On newer models the Room Sensor port is yellow 8 instead of black to help differentiate it from the black Ethernet ports NOTE For more information see Sample BAC 9311 Wiring on page 7 and the YouTube video KMC Conquest Wiring BAC 9300 Series Unitary Controllers 14 CAUTION Do NOT connect 24 VAC to the analog outputs UO7 UO10 and GNDs NOTE Use 24 VAC only with triac outputs BO1 BO6 w...

Page 4: ... the amber COMM LED remain OFF check the power and cable connections to the controller CONNECT OPTIONAL MS TP NETWORK 1 For BAC 93x1 93x1C models only connect the BACnet network to the gray BACnet MS TP terminal block 15 15 NOTE Use 18 gauge AWG shielded twisted pair cable with maximum capacitance of 51 picofarads per foot 0 3 meters for all network wiring Belden cable 82760 or equivalent A Connec...

Page 5: ...etwork 22 21 Amber ETHERNET LED 22 The amber Ethernet LED flashes when the controller is communicating with a 100BaseT Ethernet network The amber Ethernet LED remains OFF when the powered controller is communicating with the network at only 10 Mbps instead of 100 Mbps NOTE If both the green and amber Ethernet LEDs remain OFF check the power and network cable connections MS TP NETWORK ISOLATION BUL...

Page 6: ...mate K factor from the chart in the Appendix K Factors for VAV section in the KMC Conquest Controller Application Guide For instructions on VAV balancing With an STE 9000 series NetSensor see the VAV Airflow Balancing with an STE 9xx1 section of the KMC Conquest Controller Application Guide With a BAC 5051E Router see its application and installation guide With KMC Connect or TotalControl see the ...

Page 7: ...E For Ethernet models connect the controller to the network with a standard Ethernet patch cord NOTE Analog inputs accept 1K or 10K sensors 0 12 VDC or 4 20 mA NOTE For more wiring examples see the wiring diagrams that are part of the application library in KMC Connect Converge or TotalControl Early models shown in the drawings had different terminal locations Follow the terminal labels not locati...

Page 8: ...ff BO5 Binary Heating Valve On Off BO6 Binary Output 6 BO6 Binary Output 6 AO7 and BO4 are controlled simultaneously AO8 and BO5 are controlled simultaneously AO7 and BO4 are controlled simultaneously AO8 and BO5 are controlled simultaneously BAC 9301 HPU BAC 9311 HPU Inputs Inputs AI1 Space Sensor on Room Sensor port AI1 Space Sensor on Room Sensor port AI2 Space Setpoint Offset on port AI2 Space...

Page 9: ...tage 2 BO3 Cool Stage 2 BO4 Binary Output 4 BO4 Binary Output 4 BO5 Heating Stage 1 BO5 Heating Stage 1 BO6 Heating Stage 2 BO6 Heating Stage 2 BAC 9311 VAV Inputs AI1 Space Sensor on Room Sensor port AI2 Space Setpoint Offset on port AI3 UI3 Discharge Air Temperature AI4 UI4 Analog Input 4 AI5 UI5 Analog Input 5 AI6 UI6 Analog Input 6 AI7 UI7 Analog Input 7 AI8 UI8 Primary Damper Position AI9 Pri...

Page 10: ...amages direct or incidental arising out of or related to the use of this document The KMC logo is a registered trademark of KMC Controls Inc All rights reserved TEL 574 831 5250 FAX 574 831 5252 EMAIL info kmccontrols com REPLACEMENT PARTS HPO 0055 Replacement Network Bulb Module for Conquest Controllers Pack of 5 HPO 9901 Conquest Hardware Replacement Parts Kit NOTE HPO 9901 includes the followin...