HPO-9007 Series Gateways Installation Guide 

5 923-019-05B

REM AV2 = The Desired Setpoint 

Offset (such as a maximum of +/- 3 

degrees)

REM AV48 = The Potentiometer (0-

255) Value from the STW-6014 

Sensor

REM AV49 = Setpoint (Total) Range 

(such as a relinquish default of 6 

degrees)

AV2@8 = AV49 / ( 255 / AV48 ) - 

AV49 / 2

3.  In the Program Object, be sure that 

Run on 

Coldstart

 is checked in the General Properties 

section and click 

Save Changes

.

4.  For an STW-6014 setpoint offset, in 

[PRG1] 

SETPOINTS-MODES

, also add REM in front of 

the line “U = DS1.KMC_STAT_STATUS”:

REM U = DS1.KMC_STAT_STATUS

5.  If using an STW-6014 setpoint offset, 

configure MSV10’s 

Relinquish Default

 to 

[9] 

STE-6014/7

 and click 

Save Changes

.

6. 

Configure other 

Relinquish Defaults

 and 

Units

 

of relevant AV or BV objects as needed and 

click 

Save Changes

.

7.  Restart the controller and check the operation.

NOTE: 

Because the wireless sensors normally 

transmit only several times per hour 

to conserve power, 

allow at least 

30 minutes for transmissions to be 

received and all the relevant object 

values to be updated

 when verifying 

normal operation.

NOTE: 

When sensor values change beyond 

their threshold, however, a signal will be 

transmitted within a few minutes.

NOTE: 

Momentarily pressing the Learn 

button sends a new (identification) 

transmission immediately, but that 

transmission does 

not

 include sensor 

temperature, setpoint, or humidity 

values.

USE OF HPO-9001 DISTRIBUTION MODULE

To use multiple HPO-9007 gateways (and/or STE-

9000 series NetSensors) on a single controller, an 

HPO-9001 distribution module

 is required. The 

HPO-9001 must have 

0.1.0.0

 or later firmware.

To view the firmware version of a board using 

KMC software (see 

Software and Firmware 

Requirements on page 2

):

1.  In Network Manager, click the 

+

 in front of the 

relevant controller. 

2.  Click the 

+

 in front of 

Proprietary Objects

.

3.  Double-click 

[PRP147-1] DSDB_01

 (or 

equivalent).

4.  Click 

Proprietary Object Properties

.

5.  View the 

Value

 of 

FIRMWARE_REVISION

. If 

the firmware version is 

earlier

 than 

0.1.0.0

contact KMC Controls for assistance.

TROUBLESHOOTING

If using an HPO-9001 distribution module:
• 

Check the firmware version (see 

Use of HPO-

9001 Distribution Module on page 5

).

•  See the 

HPO-9001 Distribution Module Instal-

lation Guide

.

For all other issues, see the Troubleshooting 

section in the 

STW/THW Wireless Sensors 

Installation Guide

.

NOTE: 

If the HPO-9007 is momentarily 

unplugged or the controller 

momentarily loses power, sensor 

values will temporarily return to 0 until 

updated by a later sensor transmission. 

Summary of Contents for Conquest HPO-9007 Series

Page 1: ... into the backplate until the screw clears the cover NOTE The hex screw should remain in the backplate INTRODUCTION Complete the following steps to Mount a KMC Conquest HPO 9007NW or HPO 9007DW gateway Connect it to a KMC Conquest BAC 59xx 9xxx controller Discover wireless sensors NOTE The HPO 9007s only receive signals from sensors They do not transmit signals to devices NOTE See the data sheet a...

Page 2: ...nnect software ver 1 0 13 x or later KMC TotalControl software ver 4 5 0 x or later See the documents or Help systems for the respective KMC tools for more information If the the HPO 9007 is connected to an optional HPO 9001 NetSensor distribution module for use Hex Screw 2 Pull the cover off the backplate CONNECT ETHERNET CABLE 3 Feed the Ethernet patch cable from the Conquest controller through ...

Page 3: ...that is inside of the sensor body Add Sensors Method 1 Automated KMC Sensor Discovery NOTE For devices other than KMC STW THW sensors use Method 2 1 On the back of the sensor press the Learn button on the side or top of the button body dependent on the model with a small screwdriver 2 In Gateway Sensor List Properties wait until the fields for the sensor to populate with an icon and profile NOTE I...

Page 4: ...bject column and select the relevant AV object s in the drop down box es 5 If desired click in the Location column to add a description of the sensor s location 6 Click Save Changes Configure Value and Programming Objects 1 Configure the relevant AVs as needed from the above steps e g add object names and units and click Save Changes NOTE For temperature in degrees C or humidity only you are done ...

Page 5: ...ill be transmitted within a few minutes NOTE Momentarily pressing the Learn button sends a new identification transmission immediately but that transmission does not include sensor temperature setpoint or humidity values USE OF HPO 9001 DISTRIBUTION MODULE To use multiple HPO 9007 gateways and or STE 9000 series NetSensors on a single controller an HPO 9001 distribution module is required The HPO ...

Page 6: ...ith respect to this document In no event shall KMC Controls Inc be liable for any damages direct or incidental arising out of or related to the use of this document The KMC logo is a registered trademark of KMC Controls Inc All rights reserved TEL 574 831 5250 FAX 574 831 5252 e mail info kmccontrols com 2020 KMC Controls Inc Specifications and design subject to change without notice The sensors m...

Reviews: