HPO-9007 Series Gateways Installation Guide
5 923-019-05B
REM AV2 = The Desired Setpoint
Offset (such as a maximum of +/- 3
degrees)
REM AV48 = The Potentiometer (0-
255) Value from the STW-6014
Sensor
REM AV49 = Setpoint (Total) Range
(such as a relinquish default of 6
degrees)
AV2@8 = AV49 / ( 255 / AV48 ) -
AV49 / 2
3. In the Program Object, be sure that
Run on
Coldstart
is checked in the General Properties
section and click
Save Changes
.
4. For an STW-6014 setpoint offset, in
[PRG1]
SETPOINTS-MODES
, also add REM in front of
the line “U = DS1.KMC_STAT_STATUS”:
REM U = DS1.KMC_STAT_STATUS
5. If using an STW-6014 setpoint offset,
configure MSV10’s
Relinquish Default
to
[9]
STE-6014/7
and click
Save Changes
.
6.
Configure other
Relinquish Defaults
and
Units
of relevant AV or BV objects as needed and
click
Save Changes
.
7. Restart the controller and check the operation.
NOTE:
Because the wireless sensors normally
transmit only several times per hour
to conserve power,
allow at least
30 minutes for transmissions to be
received and all the relevant object
values to be updated
when verifying
normal operation.
NOTE:
When sensor values change beyond
their threshold, however, a signal will be
transmitted within a few minutes.
NOTE:
Momentarily pressing the Learn
button sends a new (identification)
transmission immediately, but that
transmission does
not
include sensor
temperature, setpoint, or humidity
values.
USE OF HPO-9001 DISTRIBUTION MODULE
To use multiple HPO-9007 gateways (and/or STE-
9000 series NetSensors) on a single controller, an
is required. The
HPO-9001 must have
0.1.0.0
or later firmware.
To view the firmware version of a board using
KMC software (see
):
1. In Network Manager, click the
+
in front of the
relevant controller.
2. Click the
+
in front of
Proprietary Objects
.
3. Double-click
[PRP147-1] DSDB_01
(or
equivalent).
4. Click
Proprietary Object Properties
.
5. View the
Value
of
FIRMWARE_REVISION
. If
the firmware version is
earlier
than
0.1.0.0
,
contact KMC Controls for assistance.
TROUBLESHOOTING
If using an HPO-9001 distribution module:
•
Check the firmware version (see
9001 Distribution Module on page 5
).
• See the
HPO-9001 Distribution Module Instal-
For all other issues, see the Troubleshooting
section in the
NOTE:
If the HPO-9007 is momentarily
unplugged or the controller
momentarily loses power, sensor
values will temporarily return to 0 until
updated by a later sensor transmission.