CTE-3016/3017/3026/3027
2
Installation Guide
© 2010 KMC Controls, Inc.
717-019-21B
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com; info@kmccontrols.com
Accessories
HMO-4523
Capillary Clip (3 or 5 provided,
depending on length)
Important Notices
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice. KMC
Controls, Inc. makes no representations or warran-
ties with respect to this document. In no event shall
KMC Controls, Inc. be liable for any damages, direct
or incidental, arising out of or related to the use of
this document.
Specifications
Maintenance
No routine maintenance is required. Each compo-
nent is designed for dependable, long-term reliabil-
ity, and performance. Careful installation will also
ensure long-term reliability and performance.
Setpoint Adjustment
The setpoint is the temperature at which contacts
“11–14” and “21–24” open as the unit senses a fall in
temperature. To adjust the setpoint:
• Turn the range adjustment screw CW to decrease
the setpoint.
• Turn the range adjustment screw CCW to
increase the setpoint.
Testing
A manual test lever located under the cover (below
and to the left of the controller spring) allows the
unit to be manually actuated during system tests.
Actuation and Reset
Terminals 11 and 21 are “common” terminals, 14
and 24 are Normally Closed (above setpoint), and
12 and 22 are Normally Open (see the diagram
below). When the sensed temperature falls below
setpoint, connections “11–14” and “21–24” open and
connections “11–12” and “21–22” close.
The switch
latches in this position until the sensed temperature
rises 5° F (3° C) above setpoint and the controller is
reset either (depending on the model) automatically
or manually by depressing the reset button located in
the top of the controller case.
The controller cannot be manually reset until the
sensed temperature is at least 5° F (3° C) above the
setpoint.
Range
34° to 70° F (1.1° to 21° C)
Differential
4.5° F fixed (2.5° C)
Switch Action
DPDT
Element
3/32" (2.4 mm) diameter, 6-foot
(183 cm) or 20-foot (607 cm)
length, vapor-filled, tin-plated
copper capillary, maximum
temperature 300° F (149° C)
Electrical Ratings
Inductive
14 FLA (Full Load Amperes)
@ 120 VAC, 12 FLA @ 240 VAC
84 LRA (Locked Rotor
Amperes) @ 120 VAC, 72 LRA
@ 240 VAC
3/4 HP @ 120 VAC, 2 HP @ 240
VAC
Pilot Duty
720 VA max. @ 120 to 600 VAC,
144 VA max. @ 24 VAC
Approvals
CUL US Listed, CE Compliant,
RoHs compliant
Weight
1.2 lbs. (0.54 kg)
Materials
Plated steel case, plastic cover
Mounting
Surface mount with capillary
installed in horizontal serpen-
tine pattern
Temperature Limits
Operating
–60 to 160° F (–51 to 71° C)
Shipping
–60 to 160° F (–51 to 71° C)
NOTE: See the CTE-3016/3017/3026/3027 Data
Sheet (717-035-21) for more information.
21
(Common)
22 (NO)
24 (NC)
(Connections Shown in Above-Setpoint, NC, Unactuated Position)
11
(Common)
12 (NO, Closes
on Low Temp.)
14 (NC, Opens
on Low Temp.)