CTE-3016/3017/3026/3027 

Installation Guide

© 2010 KMC Controls, Inc.   

717-019-21B

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com; info@kmccontrols.com

Accessories

HMO-4523 

Capillary Clip (3 or 5 provided, 

depending on length)

Important Notices

The material in this document is for information 

purposes only. The contents and the product it 

describes are subject to change without notice. KMC 

Controls, Inc. makes no representations or warran-

ties with respect to this document. In no event shall 

KMC Controls, Inc. be liable for any damages, direct 

or incidental, arising out of or related to the use of 

this document.

Specifications

Maintenance

No routine maintenance is required. Each compo-

nent is designed for dependable, long-term reliabil-

ity, and performance. Careful installation will also 

ensure long-term reliability and performance.

Setpoint Adjustment

The setpoint is the temperature at which contacts 

“11–14” and “21–24” open as the unit senses a fall in 

temperature. To adjust the setpoint:
•  Turn the range adjustment screw CW to decrease 

the setpoint.

•  Turn the range adjustment screw CCW to 

increase the setpoint.

Testing

A manual test lever located under the cover (below 

and to the left of the controller spring) allows the 

unit to be manually actuated during system tests.

Actuation and Reset

Terminals 11 and 21 are “common” terminals, 14 

and 24 are Normally Closed (above setpoint), and 

12 and 22 are Normally Open (see the diagram 

below). When the sensed temperature falls below 

setpoint, connections “11–14” and “21–24” open and 

connections “11–12” and “21–22” close. 

The switch 

latches in this position until the sensed temperature 

rises 5° F (3° C) above setpoint and the controller is 

reset either (depending on the model) automatically 

or manually by depressing the reset button located in 

the top of the controller case.

The controller cannot be manually reset until the 

sensed temperature is at least 5° F (3° C) above the 

setpoint.

Range 

34° to 70° F (1.1° to 21° C)

Differential 

4.5° F fixed (2.5° C)

Switch Action 

DPDT

Element

 

3/32" (2.4 mm) diameter, 6-foot 

(183 cm) or 20-foot (607 cm) 

length, vapor-filled, tin-plated 

copper capillary, maximum 

temperature 300° F (149° C)

Electrical Ratings

Inductive 

14 FLA (Full Load Amperes) 

@ 120 VAC, 12 FLA @ 240 VAC

   

84 LRA (Locked Rotor 

Amperes) @ 120 VAC, 72 LRA 

@ 240 VAC

   

3/4 HP @ 120 VAC, 2 HP @ 240 

VAC

Pilot Duty 

720 VA max. @ 120 to 600 VAC, 

144 VA max. @ 24 VAC

Approvals 

CUL US Listed, CE Compliant,

RoHs compliant

Weight 

1.2 lbs. (0.54 kg)

Materials 

Plated steel case, plastic cover

Mounting 

Surface mount with capillary 

installed in horizontal serpen-

tine pattern

Temperature Limits

Operating  

–60 to 160° F (–51 to 71° C)

Shipping 

–60 to 160° F (–51 to 71° C)

NOTE:  See the CTE-3016/3017/3026/3027 Data 

Sheet (717-035-21) for more information.

21

(Common) 

22 (NO)

24 (NC)

(Connections Shown in Above-Setpoint, NC, Unactuated Position)

11

(Common) 

12 (NO, Closes

on Low Temp.)

14 (NC, Opens

on Low Temp.)