KMC Controls
Revision J
About the controllers
Specifications
6
Specifications
Specifications for the KMD-5205 and KMD-5270 series of controllers are
subject to change without notice.
Inputs
8 universal inputs
Key features
Software selectable for analog or digital signals.
Standard and custom units of measure.
Pull-up resistors for switch contacts and other
unpowered equipment.
Connector
Removable screw terminal block, wire size
12–22 AWG
Conversion
12-bit analog–to–digital
Pulse Counting
Up to 1000 Hz
Input impedance
100 k
Ω
without pull-up resistors
Analog input range
0–5 volts DC, 4–20 milliamperes DC
Digital input range
0–5 volts DC and pulse counting
Pull-up resistors
None, 1k
Ω
and 10k
Ω
selected with movable
jumper
Outputs
8 universal outputs
Key features
Software programmable for analog or digital
signals. Standard and custom units of measure.
Slots for KMC output override boards
Connector
Removable screw terminal block, wire size
12–22 AWG
Conversion
12-bit digital-to-analog
Analog output range
0–10 volts DC, 50 milliamperes maximum
Programmable features
Control Basic programs
10 user-definable program areas
Networked points in
127 from Tier 1 controllers
512 from Tier 2 controllers
Networked points out
64 to Tier 1 controllers
64 to Tier 2 controllers
PID control loops
8 PID control loops
Program variables
256 — Software selectable as analog or digital
with standard and custom units of measure
Time keeping
Real-time clock with power backup for 72
hours.
Programmable for automatic daylight saving
time by date, day of month and time of day.
Tables
5 user defined
Schedules
Weekly schedules
8 each with 2 override days
Annual schedules
4