Configuration and software
All configuration is through internal browser based configuration pages. Requires HTML5
browser.
BACnet routing
One BACnet IP port that can be set up for any of the following protocols:
l
Normal BACnet IP network routing
l
BACnet broadcast management device with network and port address translation
l
Foreign device registration with BACnet broadcast management devices (BBMD)
l
PAD (packet assembling/disassembling) routing
One BACnet Ethernet port
Installation
Supply voltage
24 VAC (50/60 Hz) or 24 VDC; –15%, +20%; Class 2 only; non-
supervised (all circuits, including supply voltage, are power
limited circuits)
5 volts DC from powered USB connection
Supply source automatically switches to highest available
voltage
8 VA required power
Weight
Approximately 5.3 ounces (149 grams)
Case material
Green and black flame retardant plastic
Processor and memory
Processor
Processor 32-bit ARM® Cortex-M4
Memory
Configuration parameters and diagnostics are stored in
nonvolatile memory; auto restart on power failure
Regulatory and agency listings
UL
UL 916 Energy Management Equipment
RoHS
RoHS compliant (pending)
CE
CE compliant
FCC
FCC Class A, Part 15, Subpart B and complies with Canadian
ICES-003 Class A
This device complies with part 15 of the FCC Rules. Operation
is subject to the following two conditions: (1) This device may
not cause harmful interference, and (2) this device must accept
any interference received, including interference that may
cause undesired operation.
Environmental limits
Operating Temperature
32 to 120° F (0 to 49° C)
Shipping Temperature
-40 to 140° F (–40 to 60° C)
Humidity
0–95% RH, non-condensing
Section 1: Introduction
KMC Controls, Inc.
6