background image

KMD-5575 

Installation and Operation Guide

EIA-485 terminals are used for connections to a network of controllers. Refer to 

this checklist of best practices:

 

Connect the shields of the cable together at each device. Do not connect the 

cable shield to the circuit GND terminal on the KMD-5575.

 

Connect the shields to a good earth ground at only one end of the segment

tape back the shield ground at the other end.

  Use a KMC KMD-5575 repeater after every 31 controllers or if the cable length 

exceeds 4,000 feet (1,220 meters). Generally, use no more than 

four

 repeaters per 

EIA-485 (KMDigital or BACnet) network. (For smoke control applications, the 

maximum total length of the EIA-485 network cable, including all repeaters, is 

4,000 feet.)

  If the repeater is at an end-of-line position, refer to Illustration 3 and the “Con

-

figuration/EOL” section. The end-of-line connection will have only one wire 

attached to the A and B terminals.

  For reliable operation, use Belden cable model #82760 or equivalent (18-gauge, 

twisted, shielded, 50 picofarads or less) for all network terminal block 

connections.

  Connect the nodes of the network in a daisy-chain arrangement:

Connect the 

• 

A

 terminal in parallel with all other 

A

 terminals.

Connect the 

• 

B

 terminal in parallel with all other 

B

 terminals.

  “Star” networks (three or more conductors under the 

A

 and 

B

 terminals) are 

not

 

recommended. “T” networks can accomplish the same goal.

  Place a KMC KMD-5567 surge suppressor in the cable run where it exits a build

-

ing.

For smoke control applications, the maximum total length of the MS/TP network 

cable, including all repeaters, is 4,000 feet. The MS/TP communications network is 

supervised in smoke control applications, and the ground fault impedance value 

for the circuit is 0 ohms. For specific information on smoke control systems, see 

Smoke Control Manuals 000-035-08 (BACnet) and/or 000-035-09 (KMDigital).

Configuration/EOL

Prior to operating the KMC KMD-5575 Network Repeater-Isolator Module, you 

may need to configure the module for an End-of-Line (EOL) termination. See Il

-

lustrations 3 through 5.

If the module is connected to the network segment in an end-of-line position (only 

one set of wires connected to the terminal—refer to “Network Connections” sec

-

tion), place the EOL jumper in the “On” (shorted) position. If the module is not 

connected in an end-of-line position (two sets of wires connected to the terminal), 

then leave the jumper in the default “Off” position.

Power Connection

Before connecting power, make certain all connections and EOL jumper positions 

are complete and correct. Connect a KMC Controls 24 VAC Class-2 (power limit

-

ed) transformer of the appropriate size to the two power connections on the lower 

terminal strip. Connect the ground side of the transformer to the 

 terminal and 

the AC phase to the 

~

 (phase) terminal. See Illustration 3.

For smoke control applications, the KMC XEE-6112-100 transformer is required. 

See Smoke Control Manuals 000-035-08 (BACnet) and/or 000-035-09 (KMDigital) 

for smoke control application information.

Summary of Contents for KMD-5575

Page 1: ... Operation Guide KMD 5575 Network Repeater Isolator 873 019 02D Contents Introduction 3 Installation 3 Mounting 3 Wiring and Terminal Blocks 4 Network Connections 4 Configuration EOL 7 Power Connection 7 Indicators and Operation 8 Accessories 8 Specifications 8 ...

Page 2: ...ols Inc Printed in U S A Disclaimer The material in this document is provided for information purposes only The contents and the product s described herein are subject to change without notice KMC Controls Inc makes no representations or warranties with respect to this document In no event shall KMC Controls Inc be liable for any damages direct or incidental arising out of or related to the use of...

Page 3: ...tration 1 shows the major module components and their connections Illustration 1 Components Status LEDs Network 2 Connections Network 1 Connections Power Connection EOL Terminations Circuit Ground Repeater KMD 5575 STATUS 2 1 EOL A B GND EOL A B NETWORK 2 NETWORK 1 24 VAC NETWORK 1 2 Installation Mounting Fasten the KMC KMD 5575 securely to a flat surface inside a metal enclosure using 6 hardware ...

Page 4: ...ower Limited Network Connections The KMD 5575 Network Repeater Isolator is designed to operate between net work segments Each network is connected to the respective terminals on the module See Illustration 1 Connect the shields of the cable together at each device on that segment Connect the shields to an earth ground only at one end of the segment Do NOT connect the cable shield to the circuit se...

Page 5: ...segment Illustration 4 Repeater in a single T or Branch Sublan Configuration 24 VAC A T or Branch B Segment Y A Previous Controller B on Segment X A Next Controller B on Segment X EOL Jumper Removed EOL Jumper Installed Shield Grounded Shields Connected Shields should be connected to an earth ground at only one end of the segment Repeater KMD 5575 STATUS 2 1 EOL A B GND EOL A B NETWORK 2 NETWORK 1...

Page 6: ...one end of the segment Other Segment X Controllers Other Segment X Controllers Repeater KMD 5575 STATUS 2 1 EOL A B GND EOL A B NETWORK 2 NETWORK 1 24 VAC NETWORK 1 2 Repeater KMD 5575 STATUS 2 1 EOL A B GND EOL A B NETWORK 2 NETWORK 1 24 VAC NETWORK 1 2 Repeater KMD 5575 STATUS 2 1 EOL A B GND EOL A B NETWORK 2 NETWORK 1 24 VAC NETWORK 1 2 Shields Connected EOL Jumper Removed EOL Jumper Installed...

Page 7: ...ace a KMC KMD 5567 surge suppressor in the cable run where it exits a build ing For smoke control applications the maximum total length of the MS TP network cable including all repeaters is 4 000 feet The MS TP communications network is supervised in smoke control applications and the ground fault impedance value for the circuit is 0 ohms For specific information on smoke control systems see Smoke...

Page 8: ...15 20 60 Hz 3 VA Class 2 only NOTE All circuits including supply voltage are power limited AC power is non supervised in smoke control applications Baud Rate 9 600 to 38 400 Connections Removable screw terminal blocks wire size 14 22 AWG Network Wiring Belden 82760 or equivalent shielded twisted 18 AWG 5 5 ohms per 1 000 feet and 51 pF foot network connections are supervised in smoke control appli...

Reviews: