background image

KMC Controls

19476 Industrial Drive

New Paris, IN  46553

 574.831.5250

www. kmccontrols.com

016-019-01

Adjustments and Calibration

DANGER

The MCP-1160 contains a large powerful spring.
Exercise extreme caution if disassembly is required.
The actuator shaft MUST be restrained to prevent
the spring from expanding.

The MCP-1160 contains an 8-13 psi spring. A
positioner allows the unit to operate over any 5 psi
span with the start-point adjustable from 3-10 psi.
Replace the 5 psi spring with a 10 psi spring to widen
the span.

To change the positioner start-point:

1. Apply the desired signal pressure

2. Rotate the start-point adjuster until the actuator

starts to stroke.

Maintenance

The MCP-1160 actuator is designed for long term
reliability. No routine maintenance is required,
however care should be taken during any installation
or maintenance due to the power of the actuator.