REE-5001 

Installation Guide

Installation Guide

Triac Relay Module, 3-Stage Reheat

REE-5001 

 

CTE-5100 SERIES

REVERSE ACTING THERMOSTAT

~

Mounting 

1

Connections and Wiring  1
Sample Application  2
Troubleshooting  2
Maintenance 

2

Important Notices  2

Mounting

The 

REE-5001 may be mounted directly to a control 

box surface or in a 2 x 4" electrical handy box. Add a 

blank cover to conceal the module if desired.

Connect as shown below and/or in the sample 

illustration on the next page. Supply the relay with 

24 VAC, +20%/ –15%. (Use wire size of 14 to 22 AWG, 

stranded.)
NOTE:  Triac outputs

 are for 24 VAC loads only.

Check the graph for thermostat signal setpoints and 

corresponding stages. Stage 1 turns on at 3.5 VDC, 

Stage 2 at 6.5 VDC, and Stage 3 turns on at 9.5 VDC.
NOTE:  There is a 2 VDC switching differential on 

each stage.

Connections and Wiring