Procedure
Detailed steps
Sensor display
1. Press the
or
buttons to set the minimum
cooling setpoint. The setpoint will change in 0.5°
increments.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
4
Set the maximum heating
setpoint.
This setpoint limits the highest temperature a user can
enter as the active setpoint.
1. Press the
or
buttons to set the maximum
heating setpoint. The setpoint will change in 0.5°
increments.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
MAX
78O
5
Set the occupied cooling
setpoint.
This setpoint is used as the active setpoint when the
space is occupied.
1. Press the
or
buttons to set the occupied
cooling setpoint. The setpoint will change in 0.5°
increments.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
Note:
This setpoint can also be changed as
described in the topic
OCCL
74O
6
Set the occupied heating
setpoint.
This setpoint is used as the active setpoint when the
space is occupied.
1. Press the
or
buttons to set the occupied
heating setpoint. The setpoint will change in 0.5°
increments.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
Note:
This setpoint can also be changed as
described in the section
OCHT
7OO
Procedure to set the temperature setpoints (continued)
Section 4: Configuring the controllers
KMC Controls, Inc.
24
Revision H
Summary of Contents for SimplyVAV BAC-8001
Page 1: ...SimplyVAV Application and Installation Guide Revision H ...
Page 12: ...Section 1 About the controllers KMC Controls Inc 12 Revision H ...
Page 48: ...Section 6 Application drawings KMC Controls Inc 48 Revision H ...
Page 62: ...Section 7 Sequences of operation KMC Controls Inc 62 Revision H ...
Page 72: ...Appendix A K factors KMC Controls Inc 72 Revision H ...