Procedure
Detailed steps
Sensor display
7
Set the unoccupied cooling
setpoint.
This setpoint is used as the active setpoint when the
space is unoccupied.
1. Press the
or
buttons to set the unoccupied
cooling setpoint. The setpoint will change in 0.5°
increments.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
UNCL
8OO
8
Set the unoccupied heating
setpoint.
This setpoint is used as the active setpoint when the
space is unoccupied.
1. Press the
or
buttons to set the unoccupied
heating setpoint. The setpoint will change in 0.5°
increments.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
UNHT
62O
9
Set the supply air temperature
changeover setpoint.
Not used in all models.
This setpoint sets the supply air temperature at which
the controller will change between heating to cooling.
1. Press the
or
buttons to set the changeover
setpoint. The setpoint will change in 1° increments.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
74
CHNG
10
Set the minimum temperature
differential setpoint.
The minimum allowable temperature value between the
cooling and heating setpoints.
1. Press the
or
buttons to set the differential
setpoint. The setpoint will change in 1° increments.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
O5
DIFF
11
Set the standby differential
setpoint.
The standby setpoint is calculated by adding or
subtracting the offset value to or from the value of the
occupied setpoint.
1. Press the
or
buttons to set the standby
differential setpoint. The setpoint will change in 1°
increments.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
OS
Procedure to set the temperature setpoints (continued)
SimplyVAV
Section 4: Configuring the controllers
Revision H
25
Summary of Contents for SimplyVAV BAC-8001
Page 1: ...SimplyVAV Application and Installation Guide Revision H ...
Page 12: ...Section 1 About the controllers KMC Controls Inc 12 Revision H ...
Page 48: ...Section 6 Application drawings KMC Controls Inc 48 Revision H ...
Page 62: ...Section 7 Sequences of operation KMC Controls Inc 62 Revision H ...
Page 72: ...Appendix A K factors KMC Controls Inc 72 Revision H ...