Procedure
Detailed steps
Sensor display
1. Press the
or
buttons to set a value for the
auxillary airflow. The setpoint changes in 1 CFM
increments.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
6
Set the heating minimum
airflow limit
1. Press the
or
buttons to set the minimum limit
for heating airflow. The setpoint will change in 1 CFM
increments.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
OO
MNHT
7
Set the heating maximum
airflow limit.
1. Press the
or
buttons to set the maximum limit
for heating airflow. The setpoint will change in 1 CFM
increments.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
3SO
MXHT
8
Set the minimum limit for fan
speed.
Not used for all models.
1. Press the
or
buttons to set the minimum limit
for the fan speed. The setpoint will change in 1%
increments.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
2O
MINF
9
Set the maximum limit for fan
speed.
Not used for all models.
1. Press the
or
buttons to set the maximum limit
for the fan speed. The setpoint will change in 1%
increments.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
1OO
MAXF
10
Set the dual duct minimum
airflow.
Not used for all models.
This setpoint is for the minimum airflow when a dual-
duct system is at temperature setpoint.
1. Press the
or
buttons.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
1OO
DLMN
Procedure to set the airflow setpoints (continued)
SimplyVAV
Section 4: Configuring the controllers
Revision H
31
Summary of Contents for SimplyVAV BAC-8001
Page 1: ...SimplyVAV Application and Installation Guide Revision H ...
Page 12: ...Section 1 About the controllers KMC Controls Inc 12 Revision H ...
Page 48: ...Section 6 Application drawings KMC Controls Inc 48 Revision H ...
Page 62: ...Section 7 Sequences of operation KMC Controls Inc 62 Revision H ...
Page 72: ...Appendix A K factors KMC Controls Inc 72 Revision H ...