Procedure
Steps
Sensor display
9
Set the temperature sensor
calibration constant.
1. Press the
or
buttons to set the calibration
constant. The setpoint will change in 0.1 minute
increments.
l
For a low input reading enter a positive correction
value.
l
For a high input reading enter a negative
correction value.
2. Press the
Set
Point
button to save the setpoint and advance
to the next function.
OO
CALIB
10
Select a new configuration
function or exit.
1. Press the
or
buttons to select one of the
following:
l
STPT
,
FLOW
,
BOX
, or
RSTR
options
l
BACK
to choose .another configuration function
l
EXIT
to return to the temperature display.
2. Press the
Set
Point
button to select the next function.
ADVC
Procedure to set the advanced options (continued)
Restore Application
Choose the RSTR function to reset the SimplyVAV controller to the original configuration and
settings. Use it also to change the units of measure to display on a SimplyVAV sensor.
There are two versions of the application program in the controller.
l
The Metric version displays temperature in Celsius and uses metric values for units of
measure.
l
The English version displays temperature in Fahrenheit and uses English values for
units of measure.
Access to the Restore Application function requires entering Password 2 which is described
in the topic
Getting started with configuration
.
Tip:
Once the following procedure is started, all steps must be completed in order.
Caution
Choosing RSTR deletes all previously configured values
including balancing values and passwords. Only the
BACnet communications settings will remain unchanged.
SimplyVAV
Section 4: Configuring the controllers
Revision H
35
Summary of Contents for SimplyVAV BAC-8001
Page 1: ...SimplyVAV Application and Installation Guide Revision H ...
Page 12: ...Section 1 About the controllers KMC Controls Inc 12 Revision H ...
Page 48: ...Section 6 Application drawings KMC Controls Inc 48 Revision H ...
Page 62: ...Section 7 Sequences of operation KMC Controls Inc 62 Revision H ...
Page 72: ...Appendix A K factors KMC Controls Inc 72 Revision H ...