Procedure
Steps
Sensor display
2
Select the
CNFG
display.
1. From the
CNFG
display, press the
or
buttons to
advance to
COMM
and the
BLNC
display.
2. Press the
Set
Point
button to select
BLNC
. The display
advances to
PRI
.
3. Press the
Set
Point
button to select
PRI
.
CNFG
COMM
BLNC
PRI
3
Measure and enter the actual
maximum primary airflow
The display begins flashing
PMAX
and also displays the
actual airflow at the bottom.
Note:
The airflow will attempt to stabilize on the
highest value for either the cooling or heating
maximum airflow even if only one mode is
operational.
Note:
The airflow displayed by the digital sensor in
this stepf is the actual, uncorrected airflow.
1. Wait for the maximum airflow value to stabilize.
2. With a flow hood, measure the actual airflow.
3. Press the
Set
Point
button to advance to the entry display.
PMAX
stops flashing.
4. Press the
or
buttons to enter the measured
airflow.
5. Press the
Set
Point
button to save the measured airflow.
The display changes to
PMIN
.
PMAX
OO
4
Measure and enter the actual
minimum primary airflow
The display begins flashing
PMIN
and also displays the
actual airflow at the bottom.
PMIN
OO
The airflow balancing procedure (continued)
Section 5: Balancing airflow
KMC Controls, Inc.
38
Revision H
Summary of Contents for SimplyVAV BAC-8001
Page 1: ...SimplyVAV Application and Installation Guide Revision H ...
Page 12: ...Section 1 About the controllers KMC Controls Inc 12 Revision H ...
Page 48: ...Section 6 Application drawings KMC Controls Inc 48 Revision H ...
Page 62: ...Section 7 Sequences of operation KMC Controls Inc 62 Revision H ...
Page 72: ...Appendix A K factors KMC Controls Inc 72 Revision H ...