Procedure
Steps
Sensor display
Note:
The airflow will attempt to stabilize on the
lowest value for either the cooling or heating
minimum airflow even if only one mode is
operational.
Note:
The airflow displayed by the digital sensor in
this step is the actual, uncorrected airflow.
1. Wait for the minimum airflow value to stabilize.
2. With a flow hood, measure the actual airflow.
3. Press the
Set
Point
button to advance to the entry display.
PMIN
stops flashing.
4. Press the
or
buttons to enter the measured
airflow.
5. Press the
Set
Point
button to save the measured airflow.
The display advances to
PRI
.
5
Advance or exit
1. Press the or buttons to select one of the following:
l
SEC
to balance the secondary VAV for dual duct
systems. Choosing
SEC
advances to the
SMAX
display. This is available only on dual duct
models.
l
BACK
to choose another commissioning function
l
EXIT
to return to the temperature display.
2. Press the
Set
Point
button to select the next function.
PRI
SEC
6
Measure and enter the actual
maximum secondary airflow
The display begins flashing
SMAX
and also displays the
actual airflow at the bottom.
Note:
The airflow displayed by the digital sensor in
this step is the actual, uncorrected airflow.
1. Wait for the maximum airflow value to stabilize.
2. With a flow hood, measure the actual airflow.
3. Press the
Set
Point
button to advance to the entry display.
SMAX
stops flashing.
4. Press the
or
buttons to enter the measured
airflow.
5. Press the
Set
Point
button to save the measured airflow.
The display advances to
SMIN
.
SMAX
OO
The airflow balancing procedure (continued)
SimplyVAV
Section 5: Balancing airflow
Revision H
39
Summary of Contents for SimplyVAV BAC-8001
Page 1: ...SimplyVAV Application and Installation Guide Revision H ...
Page 12: ...Section 1 About the controllers KMC Controls Inc 12 Revision H ...
Page 48: ...Section 6 Application drawings KMC Controls Inc 48 Revision H ...
Page 62: ...Section 7 Sequences of operation KMC Controls Inc 62 Revision H ...
Page 72: ...Appendix A K factors KMC Controls Inc 72 Revision H ...