Procedure
Steps
Sensor display
7
Measure and enter the actual
minimum secondary airflow
The display begins flashing
SMIN
and also displays the
actual airflow at the bottom.
Note:
The airflow displayed by the digital sensor in
this step is the actual, uncorrected airflow.
1. Wait for the minimum airflow value to stabilize.
2. With a flow hood, measure the actual airflow.
3. Press the
Set
Point
button to advance to the entry display.
SMIN
stops flashing.
4. Press the
or
buttons to enter the measured
airflow.
5. Press the
Set
Point
button to save the measured airflow.
The display advances to
SEC
.
SMIN
OO
8
Advance or exit
1. Press the
or
buttons to select one of the
following:
l
PRI
to balance the primary VAV for dual duct
systems
l
BACK
to choose another configuration function.
l
EXIT
to return to the temperature display.
2. Press the
Set
Point
button to select the next function.
SEC
The airflow balancing procedure (continued)
Section 5: Balancing airflow