BAC-8007
Model BAC-8007 is supplied with inputs, outputs, and sequences of operation for
the following functions.
l
Dual-duct VAV heating and cooling
l
Occupancy setback—requires STE-8201
l
System diagnostic indicators
l
Airflow balancing
Additional topics in this section
Accessories and replacement parts
Specifications
SimplyVAV controller specifications are subject to change without notice.
Inputs and outputs
All inputs and outputs are factory programmed and application specific. No field
configuration is required. For details on input and output connections, see the topic
. For a detailed listing of input and output objects, see the
topic
.
Analog inputs
Analog inputs represent BACnet analog input. Not all input are applicable or required for all
models.
Key features
Standard units of measure.
Overvoltage input protection
Connectors
RJ-45 room sensor jack
Screw terminals for wire sizes 12-26 AWG
Conversion
12–bit analog–to–digital conversion
Input range
Passive, 10 kΩ pull-up to 3.3 volts DC
Analog outputs
Analog outputs are configured to represent BACnet analog output objects. No field
configuration is required. For details on application specific output connections see the
section
.
Key features
Output short protection
Standard units of measure
Connector
Screw terminals for wire size 12-26 AWG
Conversion
12–bit digital-to-analog conversion
Output voltage
0–10 VDC
Output current
30 mA per output, 30 mA total for all analog outputs
Section 1: About the controllers
KMC Controls, Inc.
6
Revision H
Summary of Contents for SimplyVAV BAC-8001
Page 1: ...SimplyVAV Application and Installation Guide Revision H ...
Page 12: ...Section 1 About the controllers KMC Controls Inc 12 Revision H ...
Page 48: ...Section 6 Application drawings KMC Controls Inc 48 Revision H ...
Page 62: ...Section 7 Sequences of operation KMC Controls Inc 62 Revision H ...
Page 72: ...Appendix A K factors KMC Controls Inc 72 Revision H ...