A p p e n d i x A :
K - f ac t o r s
To set up a VAV controller, a K-factor must be entered into the controller. Typically, this is
part of the airflow chart that the manufacturer places on the VAV unit. If this information is
missing and not available from the manufacturer, use the K-factor in the following chart.
Duct size in inches
K-factor, CFM
K-factor, LPS
4
265
8
5
357
11
6
460
14
7
652
19
8
890
27
9
1145
34
10
1443
43
12
1972
59
14
2771
86
16
3741
111
24 x 16
6980
208
Table A–1 Start point K factors