Connecting an airflow sensor
An airflow sensor is incorporated as one of the inputs to the controller. Remove the plugs
and connect the tubing from the pitot assembly to the airflow sensor inputs next to the drive
hub.
Illustration 2–3 Airflow sensor inputs
ON CTS
1 2
COMM
READY
24VAC
T
-S
T
A
T
/
SEN
SO
R
-A
+B
S
EO
L
BACnet MS/TP
Total airflow (high) Static airflow (low)
Typically, airflow sensors are supplied by the manufacturer as part of the VAV terminal unit.
If a sensor is needed, choose a sensor listed in the topic
.
Connecting inputs and outputs
SimplyVAV series controllers have preconfigured inputs and outputs to support only the
supplied programs and applications.
l
For input and output connection information, see the topic
l
To connect room temperature sensors, see the topic
l
To connect a DAT sensor, see the topic
l
For the BACnet object descriptions of the inputs and outputs, see the topic
.
Connecting room temperature sensors
Connect any of the following sensors to the RJ-45 thermostat and sensor jack. The
controller automatically detects the type of sensor. No programming or configuration is
required.
l
STE-6010W80
l
STE-6014W80
l
STE-6017W80
l
STE-8001W80
l
STE-8201W80
SimplyVAV
Section 2: Installing the controllers
Revision H
15
Summary of Contents for SimplyVAV BAC-8001
Page 1: ...SimplyVAV Application and Installation Guide Revision H ...
Page 12: ...Section 1 About the controllers KMC Controls Inc 12 Revision H ...
Page 48: ...Section 6 Application drawings KMC Controls Inc 48 Revision H ...
Page 62: ...Section 7 Sequences of operation KMC Controls Inc 62 Revision H ...
Page 72: ...Appendix A K factors KMC Controls Inc 72 Revision H ...