Configuring the VAV Box options
The box options set the controller for the specific mechanical installation of the VAV terminal
unit. The box options include the following items.
l
The K-factor for the VAV terminal unit. If the K-factor is not available, see the topic
l
Reheat configuration (optional)
l
Fan configuration (optional)
l
Direction of damper to close
Setting the box options requires entering Password 2 which is described in the topic
Getting started with configuration
Tip:
Once the following procedure is started, all steps must be completed in order.
Procedure
Detailed steps
Sensor display
1
Starting display
1. Start at the temperature display.
2. Press the
and
buttons together.
l
If Password 2 is not required, the display
changes to
CNFG
.
l
If required, enter Password 2. The display
changes to
CNFG
when Password 2 is correct.
72
12S1
PSW2
OOOO
2
Select the box settings display.
1. From the
CNFG
display, press the
or
buttons to
show the
BOX
display.
2. Press the
Set
Point
button to select the
CNFG
options. The
display changes to
STPT
.
3. Press the
or
buttons to change the display to
BOX
.
4. Press the
Set
Point
button to select
BOX
.
CNFG
STPT
BOX
3
Set the primary VAV terminal
unit K-factor.
The K-factor is supplied by the manufacturer of the VAV
terminal unit. Typically it is on the label with the unit
airflow information.
9O4
PKFT
Procedure to set the box functions
SimplyVAV
Section 4: Configuring the controllers
Revision H
27
Summary of Contents for SimplyVAV BAC-8001
Page 1: ...SimplyVAV Application and Installation Guide Revision H ...
Page 12: ...Section 1 About the controllers KMC Controls Inc 12 Revision H ...
Page 48: ...Section 6 Application drawings KMC Controls Inc 48 Revision H ...
Page 62: ...Section 7 Sequences of operation KMC Controls Inc 62 Revision H ...
Page 72: ...Appendix A K factors KMC Controls Inc 72 Revision H ...