Floating reheat
The floating reheat application is for BAC-8005 or BAC-8205 controllers. Use this application
in hydronic systems that are controlled by an actuator with tri-state inputs. The reheat
outputs are triacs that can switch up to 1 ampere at 24 volts AC.
For cooling and heating, a duct temperature sensor is required for Discharge Air Temperature
limiting and automatic changeover. See the topic
for
instructions to enable Discharge Air Temperature limiting.
When connecting the controller to a fan powered VAV unit, the fan circuits must be
compatible with the following specifications.
l
The fan start circuit is a 24 volt AC pilot duty output.
l
The fan speed output is 0-10 volts DC.
Submittal sheets for several variations of this application are available from the
page at
.
Illustration 6–5 Floating reheat
ON CTS
1 2
COMM
READY
AI1
AI5
GND
AO4
AO3
SC
BO8
BO5
BO6
SC
BO7
24VAC
AI6
GND
AI7
T
-S
T
A
T
/
SEN
SO
R
-A
+B
S
EO
L
BACnet MS/TP
Fan
Speed
Duct
Temp
Sensor
24VAC
Fan start
24 VAC
Open
Close
Common
Section 6: Application drawings
KMC Controls, Inc.
46
Revision H