2. Intended Use
The special models P 27000-S008 universal isolators are used for galvanic
isolation and conversion of input signals from 0 ... ± 200 V to output signals
from ±0 ... 10 V or ± 0 ... 20 mA. The calibrated output signal range is selected via
DIP switches. Signal transmission is linear. By means of the broad-range mains
adapter, the units can be powered by voltages from 20 to 253 V AC/DC.
Connection is made using pluggable screw clamp terminals.
Warning against misuse
Do not operate the device outside the conditions specified by
the manufacturer, as this might result in hazards to operators or
malfunction of the equipment.
3. Configuration
3.1 Tools
A screwdriver with a width of 2.5 mm is required to open and adjust the unit
and to connect the wires to the screw clamp terminals.