4.4 VariTrans® P 42000 D3: Conductor Cross-Sections
Max.:
each 1 x 2.5 mm
2
stranded wire with ferrule
each 1 x 4 mm
2
solid
each 2 x 1.5 mm
2
stranded wire with ferrule
each 2 x 2.5 mm
2
solid
Min.:
each 1x 0.5 mm
2
solid or stranded wire with ferrule
Stripping length of conductors or ferrule length: 8 mm
The high voltage transducers of the VariTrans® 4xxxx Series shall be
installed only by qualified and suitably trained personnel authorized by
the operating company. Take measures to prevent accidental contact and
make sure that there is sufficient distance or insulation between adjacent
devices. Do not connect the device to the power supply before it is
professionally installed.
NOTICE!
Do not change the measuring range during operation. The ranges are
selected by turning an insulated rotary switch on the device front using a
screwdriver.
4.3 VariTrans® P 4200x D3
Rating Plate, Range Selection