VariTrans® P 42000 D3
Specifications (continued)
Isolation
Working voltage
(basic insulation) to
EN 61010-1
• Calibrated range selection:
Up to 2200 V AC/DC across input, output, and
power supply with overvoltage category III
and pollution degree 2
(transient overvoltage: max. 13.5 kV).
• Fixed setting / types P42100D3-nnnn
Up to 3600 V AC/DC across input, output, and
power supply with overvoltage category III
and pollution degree 2
(transient overvoltage: max. 20 kV).
Rated insulation voltage
to EN 50124-1
• Calibrated range selection:
Up to 2200 V AC/DC across input, output, and
power supply with overvoltage category III
and pollution degree 2
• Fixed setting / types P42100D3-nnnn
Up to 3600 V AC/DC across input, output, and
power supply with overvoltage category III
and pollution degree 2