Service Manual
39
Table 9
(continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
F
FA
AU
UL
LT
T
D
DE
ES
SC
CR
RIIP
PT
TIIO
ON
N
C
CO
OR
RR
RE
EC
CT
TIIV
VE
E A
AC
CT
TIIO
ON
N
Service Blk
While the unit is in Service Mode, the outlet
temperature has exceeded 185°F.
• Establish a heating load to remove the heat from the
boiler loop.
• Verify that the system is full of water and that all air
has been properly purged from the system.
• Verify that the boiler is piped properly into the heating
system. Refer to Section 6 - Hydronic Piping of the
Knight Boiler Installation and Operation
Manual for the proper piping methods for the Knight
boiler.
• Check 120 vac to the boiler pump motor on a call for
heat. If voltage is not present, check the wiring back
to the main control board. Replace the main control
board if necessary.
• If 120 vac is present on a call for heat and the boiler
pump is not operating, replace the pump.
• Verify that the boiler pump is set to the proper speed
or that the boiler pump is the proper size. Reference
Section 6 - Hydronic Piping of the Knight
Boiler Installation and Operation Manual for boiler
pump specifications.
Low 24 vac
120 vac input to the main control board has
dropped below 80 vac.
• Check 120 vac supply to the transformer.
• Check wiring connections at the low voltage terminal
strip.
• Check the wire size/length to remote devices.
• Replace the transformer.
Watch Dog Error
The main control board has detected an
internal fault.
• Replace the main control board.
Write EEProm
The main control board has detected an
internal fault.
• Replace the main control board.
CRC Parameters
The main control board has detected an
internal fault.
• Replace the main control board.
No Error Stored
The main control board has detected an
internal fault.
• Replace the main control board.
Summary of Contents for 285
Page 7: ...1 Service Service Manual 7 1 Service continued The Knight boiler display ...
Page 8: ...1 Service 8 Service Manual 1 Service Control inputs ...
Page 9: ...1 Service Service Manual 9 1 Service continued Control outputs ...
Page 42: ...4 Notes 42 Service Manual ...
Page 43: ...4 Notes Service Manual 43 ...
Page 44: ...KB SER 03 CP 3M 3 07 ...