TEMON 4-C 

Doc. N°

 MO-0368-ING 

 

Microener. - Copyright 2010  

 

 

2.1 

Date 

01.12.2008

 

Rev. 

 

Pag. 

7

 

of 

14

 

 

 

9. Programming of the Device 

 
When the device is switched on, on the display will flash the index of the internal software: later the device starts to 
display the temperature read on the measure input. 
To enter in the programming phase press the button SET for some second up to light the relative LED of signalling 
SET.    The  settings  are  indicated  in  sequence  like  showed  after;  to  go  out  of  the  programming  phase  without  to 
modify the values it’s necessary to press SET without to confirm with the ENTER key the data modified. 
To modify the value or the status it’s necessary to use 

 and 

 keys and the ENTER key to store the modification. 

The pressure of the ENTER key move automatically the programming at the successive function or value. 

 

 

9.1 - Selection of the HOLD function 

 

The  function  Hold  is  the  first  function  to set in  the  menu  programming  (SET):  in  this  phase  of  programming  the 
HOLD led switch on. 
The Hold function allows to store the alarm condition that can be rearmed only manually with the RESET button 
when the temperature are lower than the threshold set. 
If  this  function  is  disabled  it’s  possible  to  rearm  the  ALARM  with  the  RESET  button  even  if  the  temperature  is 
higher than the threshold set, while the value of temperature come back under the threshold set the alarm will be 
automatically deleted. 
 
To set the Hold function it’s necessary to use the 

 and 

 keys: 

 
OFF 

function disabled 

ON 

function enabled 

 
Press the ENTER key to confirm the operation. 

 

 
 
 
 

9.2 - Selection of the number of active inputs 

 

After the setting of the Hold 

function, it’s possible to select the number of activated inputs. 

 

It’s possible to select between 3 or 4 active inputs; in case of 3 active inputs the display T4 remain off. 

 
Select 3 or 4 inputs with 

 and 

 keys 

 
Confirm with ENTER. 

 
 
 

Set HOLD modality 

T1-T2 

T3-T4 

HOLD mode disabled 

HLD 

Off 

HOLD mode enabled 

Hld 

on 

Set active inputs 

T1-T2 

T3-T4 

Active inputs: CH1 CH2 CH3 

Ch 

All active inputs 

Ch 

Summary of Contents for MICROENER TEMON 4-C

Page 1: ...TEMON 4 C Doc N MO 0368 ING Microener Copyright 2010 FW 2 1 Date 01 12 2008 Rev 0 TEMPERATURE MONITOR DEVICE TYPE TEMON 4 C OPERATION MANUAL...

Page 2: ...entification for the communication of the serial port MODBUS RTU protocol ____________________ 9 9 9 Selection of baud rate ____________________________________________________________________________...

Page 3: ...are available two levels of alarm alarm tripped that active the commutation of the relative output relay for signalling at distance or to disable the machine under control On front of the instrument...

Page 4: ...noises it s necessary to use the following indication for the wires of measure of the Pt100 to use probes with shielded wire connected at earth and wires twisted to separate the wires of the probes fr...

Page 5: ...TEMON 4 C Doc N MO 0368 ING Microener Copyright 2010 2 1 Date 01 12 2008 Rev 0 Pag 5 of 14 7 Wiring Connection...

Page 6: ...annels 5 LED FAULT of indication failure device or thermometric probes 6 LED HOLD of indication function of manual reset activated 7 LED FAN of indication activation output of ventilation 8 push butto...

Page 7: ...in the menu programming SET in this phase of programming the HOLD led switch on The Hold function allows to store the alarm condition that can be rearmed only manually with the RESET button when the...

Page 8: ...it s necessary to select the modality of functioning ventilation 9 5 Selection threshold of disable ventilation The FAN led on with fixed light indicates this phase of programming With and keys to se...

Page 9: ...ion of address network identification for the communication of the serial port MODBUS RTU protocol NOTE This set haven t mean for the models without the serial output RS485 option installed This phase...

Page 10: ...the highest temperature With and keys to select the set choice Confirm with ENTER 9 12 Configuration of output signal NOTE This set haven t mean for the models without the analogical output option in...

Page 11: ...n temperature FDC min 5 C max 30 C and after the time in which to do the control FDC min 10 max 90 period in seconds The key is used to increase the values while the key to decrease Confirm with ENTER...

Page 12: ...old value set the flashing optical signalling will be automatically deleted 11 Diagnostic The device is provided of the thermic probes diagnostic function The condition controlled on the measure input...

Page 13: ...inputs 1 and 2 On the right display on the front panel will appear the temperature of the measure channel hotter between the inputs 3 and 4 To come back in the standard modality of measure visualizat...

Page 14: ...m depth 120mm Enclosure thermoplastic self extinguishing as UL94 V0 working temperature 10 55 C humidity max 90 storing temperature 25 80 C standards electromagnetic compatibility CEI EN 50081 2 CEI E...

Reviews: