TEMON 4-C
Doc. N°
MO-0368-ING
Microener. - Copyright 2010
2.1
Date
01.12.2008
Rev.
0
Pag.
8
of
14
9.3 -
Control ventilation
After the selection of the number of inputs, the FAN led will switch on to indicate the programming of the
ventilation control.
If 3 inputs are selected the following setting are available:
ventilation control inhibited;
fun control active on 3 inputs;
Confirm with ENTER.
If 4 inputs are selected the following setting are available:
ventilation control inhibited;
fun control active on 3 inputs;
control active only on fourth input;
Confirm with ENTER.
9.4 - Selection of the threshold of switch on and switch off ventilation
To program the threshold of enable and disable ventilation it’s necessary to select the modality of functioning
ventilation.
9.5 - Selection threshold of disable ventilation
The FAN led on, with fixed light indicates this phase of programming.
With
and
keys to select the value of temperature indicated on display
Interval of programming from 5°C up to the threshold of enable ventilation -1°C
Confirm with ENTER.
9.6 - Selection threshold of enable ventilation
The fan led on, with flashing light indicates this phase of programming.
With
and
keys to select the value of temperature indicated on display
Interval of programming from disabling thr1°C up to 200 °C
Confirm with ENTER.
Set with 3 active inputs
T1-T2
T3-T4
ventilation control inhibited
fan
off
fun control active on 3 inputs
Fan
On
Set with 4 active inputs
T1-T2
T3-T4
ventilation control inhibited
fan
off
fun control active on 3 inputs
Fan
On
control active only on fourth input
fan
4