TEMON 4-C 

Doc. N°

 MO-0368-ING 

 

Microener. - Copyright 2010  

 

 

2.1 

Date 

01.12.2008

 

Rev. 

 

Pag. 

9

 

of 

14

 

 

 

9.7 - Selection of the alarm and tripped threshold 

 

The set phase of the alarm thresholds start from the programming for the measure channel number 1. 
The ALARM led on indicates the programming of the alarm threshold: 
 
With 

 and 

 keys to select the value of temperature 

 

Interval of programming from 5°C up to the tripping threshold -1°C 

 

Confirm with ENTER. 
 
The TRIP led on indicates the programming phase of the tripping threshold. 
 
With 

 and 

 keys to select the value of temperature 

 

Interval of programming from alarm thr 1°C up to 200°C. 

 
Confirm with ENTER. 
 
Repeat the same operation for the measure channels successive. 

 

9.8 - 

Selection of address network identification for the communication of the serial port 

(MODBUS-RTU protocol)

 

 

NOTE: This set haven’t mean for the models without the 

serial output

 RS485 option installed. 

 
This phase is indicated on displays where there is 

 

value in definition on displays T1-T2, ID on displays T3-T4 

 
With 

 and 

 keys to select the number choice. 

 

The range for value accepted is from 1 to 247. 

 
Confirm with ENTER. 

 

 
 
 
 

9.9 - Selection of baud rate 

 

NOTE: This set haven’t mean for the models without the 

serial output

 RS485 option installed. 

 
This phase is indicated on displays where there is 

 

BDR on displays T1-T2, and the value to set on displays T3-T4. 

 
With 

 and 

 keys to select the baud rate choice. 

 

It’ possible to set the following values: 2,4 - 4,8 - 9,6 - 19,2 kbps. 

 
Confirm with ENTER. 

Set 

T1-T2 

T3-T4 

Set address network 

ID 

Set 

T1-T2 

T3-T4 

Baud rate: 19200 

BDR 

19.2 

Baud rate: 9600 

BDR 

9.6 

Baud rate: 4800 

BDR 

4.8 

Baud rate: 2400 

BDR 

2.4 

Summary of Contents for MICROENER TEMON 4-C

Page 1: ...TEMON 4 C Doc N MO 0368 ING Microener Copyright 2010 FW 2 1 Date 01 12 2008 Rev 0 TEMPERATURE MONITOR DEVICE TYPE TEMON 4 C OPERATION MANUAL...

Page 2: ...entification for the communication of the serial port MODBUS RTU protocol ____________________ 9 9 9 Selection of baud rate ____________________________________________________________________________...

Page 3: ...are available two levels of alarm alarm tripped that active the commutation of the relative output relay for signalling at distance or to disable the machine under control On front of the instrument...

Page 4: ...noises it s necessary to use the following indication for the wires of measure of the Pt100 to use probes with shielded wire connected at earth and wires twisted to separate the wires of the probes fr...

Page 5: ...TEMON 4 C Doc N MO 0368 ING Microener Copyright 2010 2 1 Date 01 12 2008 Rev 0 Pag 5 of 14 7 Wiring Connection...

Page 6: ...annels 5 LED FAULT of indication failure device or thermometric probes 6 LED HOLD of indication function of manual reset activated 7 LED FAN of indication activation output of ventilation 8 push butto...

Page 7: ...in the menu programming SET in this phase of programming the HOLD led switch on The Hold function allows to store the alarm condition that can be rearmed only manually with the RESET button when the...

Page 8: ...it s necessary to select the modality of functioning ventilation 9 5 Selection threshold of disable ventilation The FAN led on with fixed light indicates this phase of programming With and keys to se...

Page 9: ...ion of address network identification for the communication of the serial port MODBUS RTU protocol NOTE This set haven t mean for the models without the serial output RS485 option installed This phase...

Page 10: ...the highest temperature With and keys to select the set choice Confirm with ENTER 9 12 Configuration of output signal NOTE This set haven t mean for the models without the analogical output option in...

Page 11: ...n temperature FDC min 5 C max 30 C and after the time in which to do the control FDC min 10 max 90 period in seconds The key is used to increase the values while the key to decrease Confirm with ENTER...

Page 12: ...old value set the flashing optical signalling will be automatically deleted 11 Diagnostic The device is provided of the thermic probes diagnostic function The condition controlled on the measure input...

Page 13: ...inputs 1 and 2 On the right display on the front panel will appear the temperature of the measure channel hotter between the inputs 3 and 4 To come back in the standard modality of measure visualizat...

Page 14: ...m depth 120mm Enclosure thermoplastic self extinguishing as UL94 V0 working temperature 10 55 C humidity max 90 storing temperature 25 80 C standards electromagnetic compatibility CEI EN 50081 2 CEI E...

Reviews: