12. Visualization of the Maximum Measured Value of Temperature 

 

Pressing the 

Tmax

 key on displays appear, in modality flashing, the maximum measured value of temperature. To 

pass from the visualization of the maximum temperature T1-T3 to T2-T4 to use 

 and 

 keys. After an interval of 

about 8 seconds without to press any key the device come back to display the value of measured temperature. 
To reset the v

alue of the maximum temperature it’s necessary to go in the visualization maximum values and after 

to press at the same time Tmax and 

 

 
13. Visualization of the Channels With the Higher Temperature 

 

Press the 

HOT

 key for same second up to switch on the HOT led. 

On the left display of the front panel will appear the temperature of the measure channel hotter between the inputs 
1 and 2. 
On  the  right  display  on  the  front  panel  will  appear  the  temperature  of  the  measure  channel  hotter  between  the 
inputs 3 and 4. 
To come back in the standard modality of measure visualization press the HOT key for some second up to switch 
off the relative led of signalling. 

 

 
14. Test of the Light Signalling 

 

Press at the same time 

 and 

 keys: all of the light signalling will start to flash for some seconds. 

 

 
15. Visualization of the Measured Temperature 

 

On the display on the left of the front panel appears the temperature of the channels T1 T2 in the range   

0°C ÷ +220°C. 

On the display on the right on the front panel appears the temperature of the channel T3 T4 in the range 

 

0°C ÷ +220°C. 

Use 

 and 

 keys to change the measure channels displayed. 

 

 
16. Exclusion of the Probe Inputs Not Used 

 
If one or more inputs are not used, it’s need to connect a resistance of value included between 100 and 120 ohm, 
0.25W. 
In  the  figure  is  showed  the  connection  to  disable  the  input  Ch1.  The  same  connection  can  be  used  also  for  the 
other inputs. 

Ch1

1

2

3

R = 100 ÷ 120 ohm 
       0,25W

Summary of Contents for MICROENER TEMON 4-C

Page 1: ...TEMON 4 C Doc N MO 0368 ING Microener Copyright 2010 FW 2 1 Date 01 12 2008 Rev 0 TEMPERATURE MONITOR DEVICE TYPE TEMON 4 C OPERATION MANUAL...

Page 2: ...entification for the communication of the serial port MODBUS RTU protocol ____________________ 9 9 9 Selection of baud rate ____________________________________________________________________________...

Page 3: ...are available two levels of alarm alarm tripped that active the commutation of the relative output relay for signalling at distance or to disable the machine under control On front of the instrument...

Page 4: ...noises it s necessary to use the following indication for the wires of measure of the Pt100 to use probes with shielded wire connected at earth and wires twisted to separate the wires of the probes fr...

Page 5: ...TEMON 4 C Doc N MO 0368 ING Microener Copyright 2010 2 1 Date 01 12 2008 Rev 0 Pag 5 of 14 7 Wiring Connection...

Page 6: ...annels 5 LED FAULT of indication failure device or thermometric probes 6 LED HOLD of indication function of manual reset activated 7 LED FAN of indication activation output of ventilation 8 push butto...

Page 7: ...in the menu programming SET in this phase of programming the HOLD led switch on The Hold function allows to store the alarm condition that can be rearmed only manually with the RESET button when the...

Page 8: ...it s necessary to select the modality of functioning ventilation 9 5 Selection threshold of disable ventilation The FAN led on with fixed light indicates this phase of programming With and keys to se...

Page 9: ...ion of address network identification for the communication of the serial port MODBUS RTU protocol NOTE This set haven t mean for the models without the serial output RS485 option installed This phase...

Page 10: ...the highest temperature With and keys to select the set choice Confirm with ENTER 9 12 Configuration of output signal NOTE This set haven t mean for the models without the analogical output option in...

Page 11: ...n temperature FDC min 5 C max 30 C and after the time in which to do the control FDC min 10 max 90 period in seconds The key is used to increase the values while the key to decrease Confirm with ENTER...

Page 12: ...old value set the flashing optical signalling will be automatically deleted 11 Diagnostic The device is provided of the thermic probes diagnostic function The condition controlled on the measure input...

Page 13: ...inputs 1 and 2 On the right display on the front panel will appear the temperature of the measure channel hotter between the inputs 3 and 4 To come back in the standard modality of measure visualizat...

Page 14: ...m depth 120mm Enclosure thermoplastic self extinguishing as UL94 V0 working temperature 10 55 C humidity max 90 storing temperature 25 80 C standards electromagnetic compatibility CEI EN 50081 2 CEI E...

Reviews: