background image

 

 

TEMON 4-C 

Doc. N°

 MO-0368-ING 

 

Microener. - Copyright 2010  

 

 

2.1 

Date 

01.12.2008

 

Rev. 

 

Pag. 

3

 

of 

14

 

 

 

1. Generality 

 

The  device  of  control  temperatures  TEMON  4  is  used  in  the  control  of  electric  machine,  transformer,  motor,  etc. 
where  it’s  possible  to  control  the  temperature  level  signalling  the  critical  temperature  condition  or  to  disable  the 
machine under control. For example for the control the temperature of supplying transformer, where it’s possible to 
control the temperatures of three coils of phase and the nucleus, using the tripped output (TRIP) to cut off the load 
and eventually the functions of ventilation control. 
Another important function is the presence of one port of serial communication RS485, that allows the connection 
to system of acquisition (PC, PLC, scada, etc.) of the measure data, control and programming of the device. 
The MODBUS-

RTU is the protocol used, it’s documented in a specific manual. 

A  software  for  Windows  environment  is  available  for  a  management  of  the  devices  with  complete  function  of 
control, storing data, recording alarm, etc. 
It’s available a analogue output settable 0-20 or 4-20 mA with end-scale 200°C to join to one of channel or to the 
higher of the 4 temperature channels. 

 
2. Introduction 

 

The  device  type  TEMON  4  allows  the  control  and  the  visualization  of  temperature  read  with  probe  type  RTD 
PT100. 
For each channel of measure are available two  levels of alarm (alarm-tripped) that active the commutation of the 
relative output relay for signalling at distance or to disable the machine under control. On front of the instrument on 
a double display at 3 digit, it’s possible the visualization of the temperatures, the visualization of the status of the 
alarm of the measure channels and 5 button for the programming. The instrument is completed by the functions of 
ventilation control, storing maximum values and storing of the tripped. 

 
3. Accessories and Options 

 

accessories

:  transparent cover of frontal protection

 

options:

 

serial output RS485 
analogical output 0-20mA (4-20mA) 

 
4. Installation 

 

Foreward 

 
Read carefully the present manual before to install and use the device. 
The device described in this manual must be installed and used by personal opportunely learned. 

 
Security. 

 
Before to proceed at the installation it’s necessary verify if the device is intact and it haven’t damages caused by 
transport.  The  power  supply  must  be  compatible  with  the  tool  range.  The  instrument  installation  must  be  done  in 
total  absence  of  voltage  and  observing  the  security  norm  in  force.  All  operation  of  maintenance  and  reparation 
executed  by  not  authorized  person  are  forbidden.  If  during  of  functioning  the  device  loose  the  security,  it’s 
necessary to put it out of service and to be sure that this device will not use unintentionally. 

The use can be considered insecure when the instrument: - 

don’t function regularly / - have damage clearly 

visible / - have damage caused of transport / - is stored in bad condition 

 

Summary of Contents for MICROENER TEMON 4-C

Page 1: ...TEMON 4 C Doc N MO 0368 ING Microener Copyright 2010 FW 2 1 Date 01 12 2008 Rev 0 TEMPERATURE MONITOR DEVICE TYPE TEMON 4 C OPERATION MANUAL...

Page 2: ...entification for the communication of the serial port MODBUS RTU protocol ____________________ 9 9 9 Selection of baud rate ____________________________________________________________________________...

Page 3: ...are available two levels of alarm alarm tripped that active the commutation of the relative output relay for signalling at distance or to disable the machine under control On front of the instrument...

Page 4: ...noises it s necessary to use the following indication for the wires of measure of the Pt100 to use probes with shielded wire connected at earth and wires twisted to separate the wires of the probes fr...

Page 5: ...TEMON 4 C Doc N MO 0368 ING Microener Copyright 2010 2 1 Date 01 12 2008 Rev 0 Pag 5 of 14 7 Wiring Connection...

Page 6: ...annels 5 LED FAULT of indication failure device or thermometric probes 6 LED HOLD of indication function of manual reset activated 7 LED FAN of indication activation output of ventilation 8 push butto...

Page 7: ...in the menu programming SET in this phase of programming the HOLD led switch on The Hold function allows to store the alarm condition that can be rearmed only manually with the RESET button when the...

Page 8: ...it s necessary to select the modality of functioning ventilation 9 5 Selection threshold of disable ventilation The FAN led on with fixed light indicates this phase of programming With and keys to se...

Page 9: ...ion of address network identification for the communication of the serial port MODBUS RTU protocol NOTE This set haven t mean for the models without the serial output RS485 option installed This phase...

Page 10: ...the highest temperature With and keys to select the set choice Confirm with ENTER 9 12 Configuration of output signal NOTE This set haven t mean for the models without the analogical output option in...

Page 11: ...n temperature FDC min 5 C max 30 C and after the time in which to do the control FDC min 10 max 90 period in seconds The key is used to increase the values while the key to decrease Confirm with ENTER...

Page 12: ...old value set the flashing optical signalling will be automatically deleted 11 Diagnostic The device is provided of the thermic probes diagnostic function The condition controlled on the measure input...

Page 13: ...inputs 1 and 2 On the right display on the front panel will appear the temperature of the measure channel hotter between the inputs 3 and 4 To come back in the standard modality of measure visualizat...

Page 14: ...m depth 120mm Enclosure thermoplastic self extinguishing as UL94 V0 working temperature 10 55 C humidity max 90 storing temperature 25 80 C standards electromagnetic compatibility CEI EN 50081 2 CEI E...

Reviews: