background image

Measurement Operation

6

          To avoid damage to the Meter or to the

equipment under test, disconnect circuit power 

and discharge all high-voltage capacitors before 

measuring capacitance. Use the DC Voltage

function to confirm that the capacitor is discharged.
To measure capacitance, connect the Meter as

follows:
1. Insert the red test lead into the terminal and the

    black test lead into the COM terminal.
2. Set the rotary switch to        and press BLUE

    button to select nF measurement mode.
    • At that time, the Meter will display a fixed

       value as below which is the Meter internal fixed

       distributed capacitance value. To ensure

       accuracy when measuring a small value of 

       capacitance, the tested value must subtract

       this value, REL mode can help on that.
    • For more convenience, use the included

       multi-purpose socket for measuring capacitor

       with leads or SMT capacitor. Insert the

       capacitor to be tested into the corresponding

      “+” and “-” jack of the multi-purpose socket. 

       This method is more stable and correct for 

       small value of capacitance testing.
3. Connect the test leads across with the object

    being measured. The measured value shows on

    the display.

Note

    • It takes a longer time when the tested

       capacitor is more than 100uF
    • The LCD displays OL indicating the tested

       capacitor is shorted or it exceeds the

       maximum range.
    • When capacitance measurement has been

       completed, disconnect all the connection

       between multi-purpose socket, capacitor

       and the meter.

To measure frequency, connect the meter as

follows:
1. Insert the red test lead into the COM terminal.
2. Set the rotary switch to 

Hz%

; frequency

    measurement (Hz) is default or press 

Hz%

    button to select 

Hz

 measurement mode.

3. Connect the test leads across with the object 

    being measured. The measured value shows

    on the display.
4. If you need to measure duty cycle, press

    

Hz%

 button to select 

%

 measurement mode.

Note
    • Input amplitude: (DC electric level is zero)
    

When 10Hz ~ 10MHz: 200mV    a    30Vrms.

    • When frequency measurement has been

       completed, disconnect the connection 

       between the testing leads and the circuit

       under test, and remove the testing leads

       away from the input terminals of the Meter.

1. Set the rotary

    switch to hFE.
2. Insert the multi-purpose

    socket into the input

    terminal as

    shown on

    figure 9.
3. Insert the transistor

    to be tested into the

    corresponding

    multi-purpose socket jacks.
4. The LCD display hFE

    nearest value

Note

    • When transistor measurement has been

       completed, disconnect all the connection

       between multi-purpose socket, transistor

       and the Meter.

To use EF function, connect the Meter as follows:
1. Set the rotary switch to EF and remove the test

    lead from

    the input

    terminals.

WARNING

G. Frequency Measurement 

(See figure 8)

I Transistor hFE

Measurement

(See figure 9)

J. EF Function 

(See figure 10)

figure 8

figure 9

          To avoid personal harm, do not attempt to

 input higher than 30V rms tested frequency voltage

WARNING

figure 10

front

line

Summary of Contents for KN 8058

Page 1: ...KN 8058 Digital professional multimeter Mult metro digital profesional...

Page 2: ...lectrical symbols used on the meter and in this operating manual are explained on page 2 Rules For Safe Operation Digital multimeter KN 8058 is an auto ranging multimeter the enclosure structure desig...

Page 3: ...replacement parts The internal circuit of the meter shall not be altered at will to avoid damage of the meter and any accident Soft cloth and mild detergent should be used to clean the surface of the...

Page 4: ...nt Operation A DC AC Voltage Measurement See figure 2 B DC AC Current Measurement See figure 3 figure 2 Select To avoid harms to you or damages to the meter from electric shock please do not attempt t...

Page 5: ...Measuring Resistance See figure 4 Select figure 4 To avoid damages to the Meter or to the devices under test disconnect circuit power and discharge all the high voltage capacitors before measuring re...

Page 6: ...put terminals of the Meter WARNING E Testing Diodes See figure 6 To avoid possible damage to the meter and to the divice under test disconnect circuit power and discharge all high voltage capacitors b...

Page 7: ...en completed disconnect all the connection between multi purpose socket capacitor and the meter To measure frequency connect the meter as follows 1 Insert the red test lead into the COM terminal 2 Set...

Page 8: ...to Overload indication Display OL Battery Deficiency Display Press RANGE to enter the manual ranging mode the Meter beeps Press RANGE to step through the ranges available for the selected function the...

Page 9: ...inuous measurement less than 10 seconds at an interval more than 15 minutes Range 400 A 4000 A 40mA 400mA 4A 10A Range 400 A 4000 A 40mA 400mA 4A 10A Resolution 0 1 A 01 A 0 01mA 0 1mA 0 001A 0 01A Re...

Page 10: ...e the battery from the battery compartment 4 Replace the battery with a new 9V battery NEDA1604 6F22 or 006P 5 Rejoin the tilt stand battery compartment and case bottom and reinstall the screw To test...

Page 11: ...ucciones se explican en la p gina 11 Reglas de seguridad El mult metro digital KN 8058 es un mult metro con ajuste autom tico El dise o de la estructura de la carcasa ha adoptado la t cnica avanzada d...

Page 12: ...ticas El circuito interno del mult metro no debe modificarse a voluntad para evitar da os al mult metro y accidentes Debe utilizarse un pa o y detergente suave para limpiar la superficie del mult metr...

Page 13: ...tensi n de CD CA ver Figura 2 B Medici n de corriente de CD CA ver Figura 3 figura 2 Selector Para evitar da os personales o da os en el mult metro como consecuencia de descargas el ctricas por favor...

Page 14: ...r figura 4 Para evitar da os en el mult metro o en los dispositivos sometidos a prueba desconecte la alimentaci n del circuito y descargue todos los capacitores de alto voltaje antes de medir la resis...

Page 15: ...a os posibles en el mult metro y en el dispositivo sometido a prueba desconecte la alimentaci n del circuito y descargue todos los capacitores de alto voltaje antes de probar los diodos Para evitar da...

Page 16: ...conexiones del multifunci n el capacitor y el mult metro Para medir la frecuencia conecte el mult metro como se indica a continuaci n 1 Inserte la punta de prueba roja en la terminal Hz y la punta de...

Page 17: ...m xima 4000 frecuencia 9999 gr fico de barras anal gico de 41 segmentos Velocidad de medici n Se actualiza 2 3 veces segundo Rango Autom tico o manual Polaridad de pantalla Auto Indicaci n de sobreca...

Page 18: ...400mA 4A 10A Rango 400 A 4000 A 40mA 400mA 4A 10A Resoluci n 0 1 A 01 A 0 01mA 0 1mA 0 001A 0 01A Resoluci n 0 1 A 1 A 0 01mA 0 1mA 0 001A 0 01A Precisi n 1 0 2 1 2 3 1 5 3 Precisi n 45Hz 400Hz 1 2 5...

Page 19: ...a del compartimento de la bater a 4 Reemplace la bater a con una bater a nueva de 9 V NEDA1604 6F22 o 006P 5 Vuelva a unir el soporte de inclinaci n el compartimiento de la bater a y la parte de la ca...

Page 20: ...www knova com mx...

Reviews: