3 Function 

System information 

This device is a product of the KNX system and complies with the KNX directives. Detailed 
technical knowledge obtained in KNX training courses is a prerequisite to proper 
understanding.  
The function of this device depends upon the software. Detailed information on loadable 
software and attainable functionality as well as the software itself can be obtained from the 
manufacturer´s product database. 
Planning, installation and commissioning of the device are carried out with the aid of KNX-
certified software. Full functionality with KNX commissioning software version ETS3.0d 
onwards.  
An updated version of the product database, technical descriptions and conversion programs 
and other auxiliary programs are available on our Internet website. 

Intended use 

Switching of AC 230 V electrical loads with floating contacts 

Switching of electrically-driven Venetian blinds, shutters, awnings and similar hangings 

Mounting on DIN rail in small distributors 

Product characteristics 

Outputs can be operated manually, construction site mode 

Feedback in manual mode and in bus mode 

Scene function 

Disabling of individual outputs manually or via bus 

Characteristics switch operation 

Operation as NO or NC contacts  

Logic and restraint function 

Feedback function 

Central switching function with collective feedback  

Time functions: switch-on delay, switch-off delay, staircase lighting timer with run-on time 

Characteristics blinds operation 

Suitable for 230 V AC motors 

Blind/shutter position directly controllable 

Slat position directly controllable 

Feedback of movement status, blind/shutter position and slat position 

Forced position through higher-level controller 

Safety function: 3 independent wind alarms, rain alarm, frost alarm 

Sun protection function 

2/11 

82560023 
J:0082560023 

05.08.2013 

Switch actuator / blinds actuator 

Summary of Contents for Jung 2304.16 REG HE

Page 1: ...r SELV PELV or FELV together For parallel connection of several drives to an output it is essential to observe the corresponding instructions of the manufacturers and to use a cut off relay if necessary There is otherwise risk of irreparable damage to the drives Use only Venetian blind drives with mechanical or electronic limit switches Check the limit switches for correct adjustment Observe the s...

Page 2: ...oads with floating contacts Switching of electrically driven Venetian blinds shutters awnings and similar hangings Mounting on DIN rail in small distributors Product characteristics Outputs can be operated manually construction site mode Feedback in manual mode and in bus mode Scene function Disabling of individual outputs manually or via bus Characteristics switch operation Operation as NO or NC ...

Page 3: ...indicate the states of the outputs figure 1 Off Output switched off On Output switched on Flashes slowly Output in manual mode Flashes quickly Output disabled via continuous manual mode Operating modes Bus operation Operation via push button sensors or other bus devices Short term manual operation Manual operation locally with button field automatic return to bus operation Continuous manual mode E...

Page 4: ...Switching on permanent manual control Operation using the button field is programmed and not disabled o Press the c button for at least 5 seconds LED c is illuminated status LED A1 flashes continuous manual mode is switched on Switching off permanent manual control The device is in continuous manual mode o Press the c button for at least 5 seconds LED c is off bus operation is switched on Switchin...

Page 5: ...manual mode the corresponding status LED flashes twice briefly at intervals Re enabling outputs The device is in continuous manual mode o Press c button briefly as many times as necessary until the desired output is selected The status LED of the selected output A1 flashes twice briefly at time intervals o Press ON n and OFF o buttons simultaneously for at least 5 seconds Selected output is enable...

Page 6: ...outputs are set as blind shutter outputs Connecting switched loads Output is parameterised as a switching output CAUTION Overloading the device leads to excessive heating Damage to the device and the connected cables may result Do not exceed the maximum current carrying capacity o Connected switched loads figure 4 Figure 4 6 11 82560023 J 0082560023 05 08 2013 Switch actuator blinds actuator ...

Page 7: ...ind shutter output CAUTION Overloading the device leads to excessive heating Damage to the device and the connected cables may result Do not exceed the maximum current carrying capacity o Connect drives figure 5 Figure 5 Installing the cover It is necessary to install a cover to protect the bus connection against hazardous voltages in the connection area Figure 6 Installing the cover o Route the b...

Page 8: ...e upwards and downwards operation time of the hanging o Measure slat adjusting time between Open and Closed o Enter the measured values in the parameter setting Downwards travel in seconds and operation time extension in percent i In the case of automatic operation time detection no measurement of the hanging operation times is performed i Automatic measurement of the slat adjusting time is not po...

Page 9: ... Compact fluorescent lamps uncompensated 1000 W parallel compensated 1160 W 140 µF Mercury vapour lamps uncompensated 1000 W parallel compensated 1160 W 140 µF Connections supply and load Connection mode Screw terminal single stranded 0 5 4 mm finely stranded without conductor sleeve 0 5 4 mm finely stranded with conductor sleeve 0 5 2 5 mm Fitting width Art No 2304 16 REG HE 72 mm 4 modules Art N...

Page 10: ...rly Cause 1 Sun protection safety function forced position or manual mode is activated As long as higher order functions are active no position or scene runs are possible Hanging does not move to end position position and scene runs faulty Cause Blind shutter travelling time has been set incorrectly Correct blind shutter travelling time The hanging moves upwards before the positioning and scene ru...

Page 11: ...traße 1 58579 Schalksmühle Telefon 49 23 55 8 06 0 Telefax 49 23 55 8 06 2 04 kundencenter jung de www jung de Service Center Kupferstr 17 19 44532 Lünen Germany 11 11 82560023 J 0082560023 05 08 2013 Switch actuator blinds actuator ...