For blind/shutter drives, each pair of adjacent relay outputs forms a blind/shutter output. In each 
case the left-hand relay output 

A1, A3...

 is intended for the up direction, and the right-hand load 

output 

A2, A4...

 for the down direction.  

Output is parameterised as a blind/shutter output. 

CAUTION! 
Overloading the device leads to excessive heating. 
Damage to the device and the connected cables may result. 
Do not exceed the maximum current carrying capacity. 

Connect drives (figure 5). 

Figure 5 

Installing the cover 

It is necessary to install a cover to protect the bus connection against hazardous voltages in the 
connection area. 

Figure 6: Installing the cover 

Route the bus line towards the rear. 

7/11 

82560023 
J:0082560023 

05.08.2013 

Switch actuator / blinds actuator 

Summary of Contents for Jung 2304.16 REG HE

Page 1: ...r SELV PELV or FELV together For parallel connection of several drives to an output it is essential to observe the corresponding instructions of the manufacturers and to use a cut off relay if necessary There is otherwise risk of irreparable damage to the drives Use only Venetian blind drives with mechanical or electronic limit switches Check the limit switches for correct adjustment Observe the s...

Page 2: ...oads with floating contacts Switching of electrically driven Venetian blinds shutters awnings and similar hangings Mounting on DIN rail in small distributors Product characteristics Outputs can be operated manually construction site mode Feedback in manual mode and in bus mode Scene function Disabling of individual outputs manually or via bus Characteristics switch operation Operation as NO or NC ...

Page 3: ...indicate the states of the outputs figure 1 Off Output switched off On Output switched on Flashes slowly Output in manual mode Flashes quickly Output disabled via continuous manual mode Operating modes Bus operation Operation via push button sensors or other bus devices Short term manual operation Manual operation locally with button field automatic return to bus operation Continuous manual mode E...

Page 4: ...Switching on permanent manual control Operation using the button field is programmed and not disabled o Press the c button for at least 5 seconds LED c is illuminated status LED A1 flashes continuous manual mode is switched on Switching off permanent manual control The device is in continuous manual mode o Press the c button for at least 5 seconds LED c is off bus operation is switched on Switchin...

Page 5: ...manual mode the corresponding status LED flashes twice briefly at intervals Re enabling outputs The device is in continuous manual mode o Press c button briefly as many times as necessary until the desired output is selected The status LED of the selected output A1 flashes twice briefly at time intervals o Press ON n and OFF o buttons simultaneously for at least 5 seconds Selected output is enable...

Page 6: ...outputs are set as blind shutter outputs Connecting switched loads Output is parameterised as a switching output CAUTION Overloading the device leads to excessive heating Damage to the device and the connected cables may result Do not exceed the maximum current carrying capacity o Connected switched loads figure 4 Figure 4 6 11 82560023 J 0082560023 05 08 2013 Switch actuator blinds actuator ...

Page 7: ...ind shutter output CAUTION Overloading the device leads to excessive heating Damage to the device and the connected cables may result Do not exceed the maximum current carrying capacity o Connect drives figure 5 Figure 5 Installing the cover It is necessary to install a cover to protect the bus connection against hazardous voltages in the connection area Figure 6 Installing the cover o Route the b...

Page 8: ...e upwards and downwards operation time of the hanging o Measure slat adjusting time between Open and Closed o Enter the measured values in the parameter setting Downwards travel in seconds and operation time extension in percent i In the case of automatic operation time detection no measurement of the hanging operation times is performed i Automatic measurement of the slat adjusting time is not po...

Page 9: ... Compact fluorescent lamps uncompensated 1000 W parallel compensated 1160 W 140 µF Mercury vapour lamps uncompensated 1000 W parallel compensated 1160 W 140 µF Connections supply and load Connection mode Screw terminal single stranded 0 5 4 mm finely stranded without conductor sleeve 0 5 4 mm finely stranded with conductor sleeve 0 5 2 5 mm Fitting width Art No 2304 16 REG HE 72 mm 4 modules Art N...

Page 10: ...rly Cause 1 Sun protection safety function forced position or manual mode is activated As long as higher order functions are active no position or scene runs are possible Hanging does not move to end position position and scene runs faulty Cause Blind shutter travelling time has been set incorrectly Correct blind shutter travelling time The hanging moves upwards before the positioning and scene ru...

Page 11: ...traße 1 58579 Schalksmühle Telefon 49 23 55 8 06 0 Telefax 49 23 55 8 06 2 04 kundencenter jung de www jung de Service Center Kupferstr 17 19 44532 Lünen Germany 11 11 82560023 J 0082560023 05 08 2013 Switch actuator blinds actuator ...