SAFETY PRECAUTIONS
This system is designed to provide fluid cooling only as specified in this manual. If this system is used in a
manner other than as specified, the safety protection of the system may be impaired.
Warnings are posted throughout the manual. Read and follow these important instructions. Failure to observe
these instructions or use the chiller other than as specified may impair safety protection, void the warranty, and
can result in permanent damage to the unit, significant property damage, personal injury, and/or death.
Make sure you read, understand, and follow all instructions and safety precautions listed in this manual before
operating your unit. If you have any questions concerning the operation of your unit or the information in this
manual, please contact our Applications Engineering Department at
+1-781- 933-7300
.
¾
Always turn the unit "OFF" and disconnect the power cord from the power source before
performing any service, maintenance procedures or before moving the unit.
¾
Do not operate equipment with damaged power cords.
¾
A qualified technician should perform Service and repairs.
¾
If the set point is 10° C (50° F) or below, a freezing point depressant, such as ethylene glycol, is
required. This unit is equipped with a low flow switch. This feature will shut the chiller down
during a low flow situation to prevent freezing.
¾
DO NOT USE AUTOMOTIVE ANTI-FREEZE IN THE CHILLER. The rust inhibitors in the
automotive type may cause premature failure of the pump seals. Use of automotive anti-freeze
in a Lytron chiller will void the warranty.
¾
Never place the unit in a location where excessive heat, moisture, or corrosive materials are
present.
¾
The unit must be plugged into a properly grounded power source.
¾
Do not connect the SUPPLY or RETURN fitting to your building water supply or any pressurized
source.
¾
DO NOT USE OR MAINTAIN THE CHILLER OUTDOORS. These units were not designed to
withstand outdoor weather conditions.
¾
Performance of installation, operation, or maintenance procedures other than those described
in this manual may result in a hazardous situation and may void the Lytron warranty.
¾
Transport the unit with care. Sudden jolts or drops can damage the unit.
¾
Drain the chiller of all water when transporting, shipping or leaving unused for long periods of
time. This will prevent freezing and algae build up while idle.
¾
Observe all warning labels. Never remove warning labels.
¾
Do not operate damaged or leaking equipment.
¾
Do not operate the unit without fluid in the reservoir.